ISU # Description Setting
8140 Humidification
control
0 = Humidify only when heat is On
1 = Humidify only when fan is On
2 = Humidify on demand: Thermostat controls
fan
3 = Humidify on demand: Humidifier controls fan
9100 Dehumidification
equipment
0 = None
1 = A/C with low speed fan
2 = A/C with high speed fan
4 = Whole house dehumidifier
9140 Dehumidification
equipment setup
0 = Normally open
1 = Normally closed
9160 Dehumidification -
overcooling limit
0, 1, 2, 3°F
0.0, 0.5, 1.0, 1.5°C
9180 Dehumidifier fan
control
0 = Thermostat controls fan
1 = Equipment controls fan
10100 Ventilation type 0 = None
1 = ERV / HRV
2 = Passive (fan only)
3 = Fresh air damper
10160 Ventilation fan
control
0 = Thermostat controls fan
1 = Equipment controls fan
10240 Ventilation percent
on time
10% to 100% (in 10% increments)
10280 Ventilation low
temperature
lockout
O
-20°F to 40°F (in 5°F increments)
-29.0°C to 4.5°C (in 2.5°C or 3.0°C increments)