SERIES 72 MODUTROL IV™ MOTORS
7 Based on 63-2640—08
3. Replace wiring box cover.
POWER
END
OF
JUNCTION
BOX
MOTOR
CONTROLLER
MOTOR
T1
T2
24V
1
L1
(HOT)
L2
Q5001
VALVE
LINKAGE
MOTOR
-
-
+
+
F
2
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.
2 CONNECTING F TO – WILL DRIVE MOTOR TO FULLY OPEN.
VALV E
1/4-20 UNC
1 in. LONG
MOUNTING
BOLTS
Fig. 5. Typical system wiring.
M5778
M18994
Fig. 4. Mounting the motor on a Q5001 Valve Linkage.
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect all power supplies before installation.
Motors with auxiliary switches can have more than one
disconnect.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
1. Ensure that the voltage and frequency stamped on the
motor correspond with the power supply characteristics.
2. When connecting several motors in parallel, ensure that
the power supply VA rating is large enough to provide
EXTERNAL
POTENTIOMETER
power to all motors used without overloading.
3. Fig. 10 shows that motor terminals are quick-connects
located on top of the printed circuit board.
4. To access the wiring compartment:
a. Remove the four screws from the junction box top.
b. Lift off the cover.
5. Refer to Fig. 5 through 8 for wiring.
Wire the motor as follows:
1. Remove the wiring box cover by removing the four
screws holding the cover to the motor.
2. Wire motor to system using quick-connect terminals in
wiring box.