PRODUCT DATA
63-2629—2
Series 61 and Series 62
Modutrol IV™ Motors
APPLICATION
The Series 61 and Series 62 Modutrol IV™ Motors are
three-wire spring return and non-spring return floating control
motors. Use these motors with controllers that provide a
switched spdt or floating output to operate dampers or valves.
The Series 62 motors have an internal electrically isolated
feedback potentiometer that provides indication of the motor
shaft position and can be used for slaving Series 90 Motors or
rebalancing an external control circuit.
FEATURES
Replaces M644, M944B,E,G,H,J,K,R,S and
M945B,C,G,K,L,AD Motors.
Integral junction box provides NEMA 3 weather
protection.
Integral spring return returns motor to normal position
when power is interrupted.
Motor and circuitry operate from 24 Vac. Models
available with factory installed transformer, or a field
added internal transformer.
Quick-connect terminals are standard—screw terminal
adapter is available.
Adapter bracket for matching shaft height of older
motors is available.
Motors have field adjustable stroke (90° to 160°).
Die-cast aluminum housing.
Integral auxiliary switches are available factory
mounted, or can be field added.
Nominal timing standard of 30 seconds (90° stroke),
and 60 seconds (160° stroke). Other timings available.
Spring return motors can operate valve linkages from
power end or auxiliary end shafts for normally closed
or normally open valve applications.
All models have dual shafts (slotted and tapped on
both ends).
All models have auxiliary switch cams.
Fixed torque throughout the entire voltage range.
Motors are designed for either normally open or
normally closed valves and dampers.
Series 62 models include electrically isolated feedback
potentiometer that provides shaft position indication.
Series 62 TRADELINE models have linear feedback,
configurable for slaving Series 90 Motors.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Settings and Adjustments ................................................. 7
Operation .......................................................................... 10
Checkout .......................................................................... 10
Replacement .................................................................... 10
Question and Answer IconNeed help?

Do you have a question about the Honeywell Modutrol IV M6284F1039 and is the answer not in the manual?

Honeywell Modutrol IV M6284F1039 Specifications

General IconGeneral
BrandHoneywell
ModelModutrol IV M6284F1039
CategoryEngine
LanguageEnglish

Summary

FEATURES

APPLICATION

SPECIFICATIONS

Electrical Ratings

Power consumption ratings for Series 61 and 62 Modutrol IV motors.

Auxiliary Switch Ratings

Ratings for auxiliary switches used with Modutrol IV motors.

INSTALLATION

Location

Choosing a suitable location for accessory installation and motor servicing.

Mounting

Guidelines for proper motor mounting, including crankshaft orientation and flange drilling.

Adapter Bracket

Details on using the 220738A Adapter Bracket for shaft height adjustment.

Wiring

Junction Box

Provides NEMA 3 weather protection for motor terminals.

Wiring Diagrams

Typical wiring connections for Series 61 and 62 motors.

SETTINGS AND ADJUSTMENTS

Adjustable Stroke

How to set the stroke for Series 61 and 62 motors.

Feedback Potentiometer Configuration

Feedback characteristics and shunt resistor selection for Series 62 motors.

Auxiliary Switch Adjustment

Procedure for adjusting auxiliary switch cams for desired switching points.

OPERATION

CHECKOUT

REPLACEMENT

Damper Application

Steps for replacing motors in damper applications.

Valve Application

Steps for replacing motors in valve applications.