ISU # Description Setting
10280 Ventilation low
temperature
lockout
O
-20°F to 40°F (in 5°F increments)
-29.0°C to 4.5°C (in 2.5°C or 3.0°C increments)
10300 Ventilation high
temperature
lockout
O
80°F to 110°F (in 5°F increments)
26.5°C to 43.5°C (in 2.5°C or 3.0°C increments)
10320 Ventilation high
dew point lockout
O
65°F to 85°F (in 5°F increments)
18.5°C to 29.5°C (in 2.5°C or 3.0°C increments)
11100 Home heat setpoint 40°F to 90°F
4.5°C to 32.0°C (in 0.5°C increments)
11120 Home cool setpoint 50°F to 99°F
10.0°C to 37.0°C (in 0.5°C increments)
11140 Setpoint for away
mode
0 = Away setpoints
1 = Smart temperature setpoints
11160 Away heat setpoint 40°F to 90°F
4.5°C to 32.0°C (in 0.5°C increments)
11180 Away cool setpoint 50°F to 99°F
10.0°C to 37.0°F (in 0.5°C increments)
14020 Temperature
display oset
-3°F to 3°F
14025 Humidity % oset -12% RH to 12% RH