Make sure electrical connections are clean and tight. 
Replace damaged wire with moisture-resistant No. 
18 wire rated for continuous duty up to 105
 
C [221
 
F].
 
• 
Check for cracked ceramic insulator, which can cause 
short to ground, and replace igniter-sensor if neces- 
sary.
 
• 
At the gas control, disconnect main valve wire from 
the TH or MV terminal.
 
• 
Turn on power and set thermostat to call for heat. The 
pilot should light but the main burner will remain off 
because the main valve actuator is disconnected.
 
• 
Check the pilot flame. Make sure it is blue, steady and 
envelops 3/8 to 1/2 in. [10 to 13 mm] of the flame rod. 
See Fig. 13 for possible flame problems and their 
causes.
 
• 
If necessary, adjust pilot flame by turning the pilot
 
adjustment  screw  on  the  gas  control 
clockwise  to    decrease  or 
counterclockwise   to increase pilot flame. Fol- 
lowing adjustment, always replace pilot adjustment 
cover screw and tighten firmly to assure proper gas 
control operation.
 
• 
Set thermostat below room temperature to end call 
for heat.
 
❏
 
Recheck ignition sequence as follows.
 
• 
Reconnect main valve wire.
 
• 
Set thermostat to call for heat.
 
• 
Watch ignition sequence at burner.
 
• 
If spark still doesn’t stop after pilot lights, replace 
ignition module.
 
• 
If main burner doesn’t light or if main burner lights but 
system locks out, check module, ground wire and gas 
control as described in appropriate troubleshooting 
chart, Fig. 14 or 15.
 
 
START 
 
 
NO 
 
YES 
 
NO 
 
NO 
 
 
YES 
 
 
 
YES 
 
 
 
NO 
 
 
 
NO 
 
YES 
 
 
 
 
 
NO 
 
YES 
 
 
NO 
 
YES 
 
 
NO 
 
 
YES 
 
 
  
POWER TO MODULE? 
(24V NOMINAL) 
NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min. 
nom. for retry or reset system. 
SYSTEM RUNS UNTIL 
CALL FOR HEAT ENDS? 
Check continuity of ignition cable and ground wire. 
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at 
the time of checkout. 
Check that pilot flame covers flame rod and is steady and blue. 
If checks are okay, replace module. 
NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min. 
nom. for retry or reset system. 
SPARK STOPS WHEN 
PILOT IS LIT? 
Check continuity of ignition cable and ground wire. 
Clean flame rod. 
Check electrical connections between flame rod and module. 
Check for cracked ceramic flame rod insulator. 
Check that pilot flame covers flame rod and is steady and blue. 
Adjust pilot flame. 
If problem persists, replace module. 
 
Pull ignition lead and 
check spark at module. 
TURN GAS SUPPLY OFF. 
TURN THERMOSTAT 
(CONTROLLER) TO CALL 
FOR HEAT 
 
Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Also, 
check air proving switch on combustion air blower system (if used) and that vent damper (if used) is open and 
end switch is made. 
Before troubleshooting, familiarize yourself with the startup and checkout procedure. 
NOTE: Models with TH-W terminal (7) must have call for heat 24 Vac supply connected to the TH-W terminal. 
Models with no TH-W terminal must have call for heat 24 Vac supply connected to 24V terminal (6). 
Check for proper thermostat (controller) operation. 
Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas 
control. 
Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module. 
Check electrical connections between module and gas control. If okay, replace gas control or gas control 
operator. 
Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice 
is not blocked. 
Check electrical connections between module and pilot operator on gas control. 
Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, 
replace module. 
NOTE: It may be necessary to recycle the call for heat to clear the pilot supply tubes of air. 
Check ignition cable, ground wiring, ceramic insulator and gap, and correct. 
Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and 
boot from excessive temperatures. 
 
SPARK ACROSS 
IGNITER/SENSOR GAP? 
(S8660, S8670, S8680 
HAVE 45 SECOND [NOMINAL] 
PREPURGE BEFORE SPARK 
STARTS.) 
On models with vent damper plug, make sure vent damper 
has not been installed, then removed. Replace vent damper 
if necessary. 
On other models, replace module. 
TURN GAS SUPPLY ON 
AND RECYCLE CALL 
FOR HEAT 
Repeat procedure until troublefree operation is obtained. 
 
Fig. 14—S8600, S8610 troubleshooting guide.