2. SETUP (ADVANCED OPTIONS) T775A/B/M SERIES 2000 CONTROLLER 
21 62-0254–03
Fig. 44. Setup - Sensors - Sensor B - Throttling 
Range.
2.2.4.2. THROTTLING RANGE (Sensor B only)
The throttling range for the modulating high or low limit 
positions the setpoint at the end of the throttling range. 
For example, with a high (Heat) limit at Sensor B of 200°F 
and a throttling range of 10°F, the modulating output 
controlling Sensor A begins to throttle back at 190°F, and 
fully closes at 200°F. Conversely, the throttling range for 
the low limit begins above the Cooling setpoint in the 
same manner.
1. From the Limit menu, use the T button to highlight 
THROT RNG.
2. Use the S and T buttons to increase/decrease the 
desired value for the Throttling Range.
Default = 0
3. Press the X button to accept the value and return to 
the Limit menu.
4. Press the W button to exit the Limit menu.
5. Press the W button to exit the Sensors menu and 
return to the Setup menu.
Fig. 45. Setup - Outputs Menu.
2.3. Setting up the Outputs
1. From the Setup menu, use the Sand T buttons to 
highlight OUTPUTS.
2. Press the X button to display the Outputs menu.
NOTE: The menus (e.g. the Outputs menu shown here) 
can display only those relays that are defined in 
Setup (see page 24). For example, if you config-
ure only two relays, then only two relays display 
on the appropriate menus.
The following procedures set up each modulating output 
and relay output.
Fig. 46. Setup - Outputs - Modulating Output Menu.
2.3.1. Setting up the Modulating Outputs
1. From the Output menu, use the S and T buttons to 
highlight the desired modulating output (MOD 1 or 
MOD 2).
2. Press the X button to display the selected MOD 
menu.
NOTE: Modulating outputs are not available on the 
T775A and T775B controller models. If you are 
setting up one of these controllers, skip to “2.3.2. 
NBR OF RELAYS” on page 24.
Use the remaining procedures, beginning with “2.3.1.1. 
TYPE (of output signal)”, to set up each modulating 
output. If you have two modulating outputs, repeat these 
procedures for each modulating output.
SETUP
SENSORS
SENSOR B
UNITS
CALIBRATE
LABEL
LIMIT
HI LIMIT
THROT RNG
EXIT
SETUP
SENSORS
  SENSOR  B
ENTER
VALUE FOR
SENSOR B
THROTLING
RANGE
SETUP
SENSORS
SENSOR B
THROT RNG
10
F
o 
M24510
SETUP
OUTPUTS
SETUP
OUTPUTS
MOD 1
MOD 2
# RELAYS
OPTIONS
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
M24511
SETUP
 
OUTPUTS
  MOD 1
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT %
INTEGRAL
DERIVATIV
SCHEDULE
RESET
EXIT
M24512