INSTALLATION INSTRUCTIONS
62-0254-13
T775A/B/M Series 2000
Electronic Stand-Alone
Controllers
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls
capable of remote sensing of temperature and providing
switched and/or proportional outputs to various types of
loads.
Five models have analog (modulating) outputs for
actuator and motor control, and NEMA-4 weatherproof
enclosures are available for wet environments.
IMPORT ANT
Each T775A/B/M controller is an operating
control, not a limit or safety control. If used in
applications requiring safety or limit controls, a
separate safety or limit control device is
required.
Table 1. T775A/B/M Controller Configurations.
Controller
Model
a
a
All models include a digital input for use with the disable or setback option.
Description Replaces
SPDT
Relay
Outputs
Analog
(Mod)
Outputs
b
b
The modulating (analog) outputs are 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.
Floating
Outputs
c
c
Each floating output eliminates two SPDT relays.
Sensor
Inputs
Nbr of
Sensors
Included Enclosure
T775A2009 Standard T775A1001 1 None None 1 1 NEMA 1
T775B2016 Standard N/A 2 None 1 2 1 NEMA 4X
T775B2024 Standard T775C1009 T775D1008 4 None 2 2 1 NEMA 4X
T775B2032 Standard T775A1019 T775B1000 2 None 1 2 1 NEMA 1
T775B2040 Standard T775A1027 T775A1035
T775B1018 T775B1026
T775B1042
4None2 21 NEMA 1
T775M2006 Modulating N/A None 2 N/A 2 1 NEMA 1
T775M2014 Modulating T775G1005 T775G1013
T775G1021 T775G1039
42 N/A
2
d
d
These models can support a high/low modulating limit at Sensor B for temperature control at Sensor A.
1 NEMA 4X
T775M2022 Modulating N/A 2 2 N/A
2
d
1 NEMA 4X
T775M2030 Modulating T775E1114 T775F1022
T775F1055 T775F1089
42 N/A
2
d
1 NEMA 1
T775M2048 Modulating T775E1015 T775E1023
T775E1056 T775E1064
T775E1098
22 N/A
2
d
1 NEMA 1
All manuals and user guides at all-guides.com
all-guides.com

Other manuals for Honeywell T775B2040

Question and Answer IconNeed help?

Do you have a question about the Honeywell T775B2040 and is the answer not in the manual?

Honeywell T775B2040 Specifications

General IconGeneral
BrandHoneywell
ModelT775B2040
CategoryController
LanguageEnglish

Summary

APPLICATION GUIDE AND CROSS REFERENCE

T775 Application Tips

Compatible Components

Lists sensors, humidity sensors, pressure sensors, universal sensors, and accessories.

T775 Operations

Integral Action

Explains how integral action minimizes droop and hunting by summing offset errors.

Derivative Action

Describes derivative action opposing changes and providing corrective action based on rate of change.

Differential vs. Throttling Range

Clarifies differential for relays and throttling range for modulating/floating outputs.

Setpoint High Limit

Explains setting an irreversible maximum setpoint limit for specific local code compliance.

Water Source Heat Pump Loop Water Controller – T775B

Water Source Heat Pump Loop Water Controller Application Description

Explains T775B control for loop water temp in heat pump systems, including alarms.

Water Source Heat Pump Loop Water Controller Programming Example

Details programming for boiler, low temp alarm, cooling, and high temp alarm relays.

Chiller – T775B

Chiller Application Description

Describes T775B sump water control for chillers, including freeze protection.

Chiller Programming Example

Outlines programming for spray water pump, fan control, and sump freeze protection relay.

Chiller, Rotary Compressor – T775B

Chiller Rotary Compressor Application Description

Details T775B control of discharge water temp for rotary compressors, using solenoid valves.

Chiller Rotary Compressor Programming Example

Shows programming for compressor stages controlling solenoid valves for slide valve positioning.

Cooling Tower Control – T775B2040

Cooling Tower Control Application Description

Explains T775B2040 control of cooling tower fan speeds and cold weather shutdown.

Cooling Tower Control Programming Example

Details programming for sump temp-based fan speeds and outdoor temp-based cutoff.

Time-based Control of Fan, Pump, etc. – T775 (all models)

Time-based Control Application Description

Describes T775 control of devices like fans or pumps based on a daily time schedule.

Time-based Control Programming Example

Shows how to program a relay for timed operation of a fan, pump, or other device.

Damper or Valve Modulation – T775M or T775R

Damper or Valve Modulation Application Description

Explains T775M control of actuators to modulate dampers or valves based on temperature.

Damper or Valve Modulation Programming Example

Details programming for modulating output to control an actuator via setpoint and throttling range.

Hot Water Reset – T775R

Hot Water Reset Application Description

Describes T775R control of boiler water temp with two stages using a reset curve.

Hot Water Reset Programming Example

Shows how to program reset curves and setpoint offsets for boiler discharge temperature.

Chilled Water Reset – T775R

Chilled Water Reset Application Description

Explains T775R control of chiller water temp using a reset curve and offsets for multiple stages.

Chilled Water Reset Programming Example

Details programming for a reset curve to control chiller water temperature based on outside air.

Multi-Stage Boiler Control (No Reset) – T775P

Multi-Stage Boiler Control (No Reset) Application Description

Describes T775P multistage boiler control using discharge water temp and a primary pump relay.

Multi-Stage Boiler Control (No Reset) Programming Example

Shows programming for stages, pump control, alarms, and temperature setpoints.

Multi-Stage Boiler Control (Reset) – T775P

Multi-Stage Boiler Control (Reset) Application Description

Explains T775P multistage boiler control with reset based on discharge water temperature.

Multi-Stage Boiler Control (Reset) Programming Example

Details programming for reset curves, stages, and pump control for boiler systems.

Multi-Stage Chiller Control (No Reset) – T775P

Multi-Stage Chiller Control (No Reset) Application Description

Describes T775P multistage chiller control based on discharge water temp, using a pump relay.

Multi-Stage Chiller Control (No Reset) Programming Example

Shows programming for chiller stages, pump control, and low alarm settings.

4 Stage with Pump Output and Reset – T775P using a T775S Expansion Module

4 Stage with Pump Output and Reset Application Description

Details T775P control of multistage boilers with pump output using an expansion module.

4 Stage with Pump Output and Reset Programming Example

Outlines programming for 4 stage boiler control, pump output, and reset curves.

3 Stage Reciprocating Chiller – T775L

3 Stage Reciprocating Chiller Application Description

Explains T775L control for reciprocating chillers with freeze protection and low temp cutoff.

3 Stage Reciprocating Chiller Programming Example

Shows programming for chiller cooling stages and freeze protection using sensors.

4 Stage Heat and 6 Stage Cool – T775L

4 Stage Heat and 6 Stage Cool Application Description

Describes T775L control for multiple boilers and multistage cooling using different sensors.

4 Stage Heat and 6 Stage Cool Programming Example

Details programming for staged heating and cooling loops with separate setpoints and ranges.

Pressure with a Variable Frequency Drive (VFD) – T775U

Pressure with Variable Frequency Drive Application Description

Explains T775U control of duct pressure via fan speed using a VFD and pressure sensor.

Pressure with Variable Frequency Drive Programming Example

Shows programming for pressure sensor input and a 4-20mA PID modulating output to the VFD.

Carbon Dioxide (CO2) Sensing – T775U

Carbon Dioxide Sensing Application Description

Describes T775U control of an outside air damper based on CO2 sensing input for air quality.

Carbon Dioxide Sensing Programming Example

Details programming for CO2 sensor input and setting units for ppm.

Resetting Zone Air Temp Based on Outside Air Temp (2 stage cooling)

Resetting Zone Air Temp Based on Outside Air Description

Explains T775L two-stage cooling based on zone temp, using outside air temp for reset.

Resetting Zone Air Temp Based on Outside Air Programming Example

Shows programming for zone air temp reset using a reset curve based on outdoor temperature.

Resetting Discharge Air Temp Based on Return Air Temp (Modulating cooling valve)

Resetting Discharge Air Temp Based on Return Air Description

Details T775R control of discharge air temp based on return air temp using a reset curve.

Resetting Discharge Air Temp Based on Return Air Programming Example

Shows programming for discharge temp setpoint modulation based on actual return air temperature.

Using the T775R as a Differential Temperature Controller for Solar Water Heating

Using T775R for Solar Water Heating Application Description

Explains T775R as a differential controller for solar water heating, regulating circulation pump.

Using T775R for Solar Water Heating Programming Example

Details programming for pump turn-on/off based on differential, high limit, and low limit.

Maintaining Differential Temperature for both Heating and Cooling

Maintaining Differential Temperature for Heating and Cooling Description

Describes T775R maintaining differential temp between room and outside air for free heating/cooling.

Maintaining Differential Temperature for Heating and Cooling Programming Example

Shows programming for cooling and heating engagement based on temperature delta and reset curves.

T775M2030 Replacement for W973A Logic Panel

T775M2030 Replacement for W973A Logic Panel Description

Illustrates replacing a W973A Logic Panel with a T775M2030 for two-stage Heat/Cool control.

T775M2030 Replacement for W973A Wiring

Shows wiring connections for the W973A Logic Panel as a pre-existing control.

T775R Replacement for W964F Aquatrol Panel with Floating Actuator

T775R Replacement for W964F Aquatrol Panel Description

Explains replacing a W964F Aquatrol Panel with a T775R for floating actuator control.

T775R Replacement for W964F Aquatrol Panel Wiring

Displays wiring connections for the W964F Aquatrol Panel as a pre-existing control.

T775L Replacement for S984 Step Controller

T775L Replacement for S984 Step Controller Description

Illustrates replacing an S984 Step Controller with a T775L using an expansion module.

T775L Replacement for S984 Step Controller Wiring

Shows wiring connections for the S984 Step Controller as a pre-existing control.

T775L Replacement for W7100C Discharge Air Controller

T775L Replacement for W7100C Discharge Air Controller Description

Explains replacing a W7100C controller with a T775L for two-stage heat and four-stage cool.

T775L Replacement for W7100C Discharge Air Controller Wiring

Displays wiring connections for the W7100C Discharge Air Controller as a pre-existing control.

T775 Cross Reference

T775 Cross Reference: Johnson System 350

Lists T775 electronic replacements for Johnson System 350 controls, detailing features and specs.

Honeywell Controls

T775 Cross Reference: Honeywell Controls

Provides a cross-reference for Honeywell controls to T775 electronic replacements, listing features.

White Rodgers Controls

T775 Cross Reference: White Rodgers Controls

Lists T775 electronic replacements for White Rodgers controls, including temperature ranges and features.

Barber Colman Controls

T775 Cross Reference: Barber Colman Controls

Provides a cross-reference for Barber Colman controls to T775 electronic replacements, detailing features.

Ranco Controls

T775 Cross Reference: Ranco Controls

Lists T775 electronic replacements for Ranco controls, matching various model numbers.

Tekmar Model & T775 Cross Reference

Tekmar Model and T775 Features Comparison

Compares features of Tekmar models with various T775 electronic controllers, highlighting differences.