INSTALLATION INSTRUCTIONS
E4436
T775P Series 2000 Electronic 
Stand-Alone Controller
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next 
generation of commercial and agricultural controls 
capable of remote sensing of temperature and providing 
switched and/or proportional outputs to various types of 
loads. A built-in time clock is standard.
The T775P can be configured with or without Reset 
control from a single heat or cool setpoint.
Three sensors are configurable. In normal installations, 
Sensor A is the supply controlled temperature, Sensor B 
is the outdoor controlling (reset) temperature, and 
Sensor C is the return controlled temperature, which can 
be used for the Differential alarm and/or as the controlled 
setpoint sensor.
The T775P can be configured with up to two T775S 
Expansion Modules for a maximum of up to 12 stages 
with the last stage being an option for a pump stage.
IMPORTANT
The T775P is an operating control, not a limit or 
safety control. If used in applications requiring 
safety or limit controls, a separate safety or limit 
control device is required.
 
Table 1. T775P Controller Configuration.
Controller Model Description
Output
Reset
SPDT Relay
Outputs
Digital
Output
Digital
Input
Sensor
Inputs
Number of
Sensors
Included
Stage
 Control
Addable
 T775S Enclosure
T775P2003
a
Boiler 
Model
with Reset
Yes
4
b
1
1
c
33YesYesNEMA 1
a
The T775P model can be used to stage multiple relays from a single heat or cool setpoint. The number of stages can be freely chosen, limited 
by the number of relays available (up to 12 stages [11 if using the pump output] using two T775S expansion modules).
b
The T775P provides a pump output using the last of the four SPDT relay outputs on the T775P controller. When T775S Expansion Modules are 
used, the configurable pump output is the last relay output of the last expansion module. The pump output will be either stage 4, 8, or 12, 
depending on whether T775S Expansion module(s) are used.
c
The T775P includes a digital input for use with the disable or setback option.