T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0256—11 6
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and 
are described in Table 2. 
See Fig. 8 – Fig. 12 beginning on page 7 for typical 
T775P wiring applications.
Fig. 7. T775P Terminal and Feature Locations.
NOTES:
1. Relays 5–8 are assigned to the first T775S 
Expansion Module, if connected. Relays 9–12 
are assigned to the second T775S, if 
connected. 
2. If Expansion Modules are used, the pump 
output is always the last relay output, 8 or 12 
respectively.
WIRING APPLICATION 
EXAMPLES
Fig. 8 – 12 beginning on page 7 illustrate typical controller 
wiring for various applications.
NOTE: The Electronic Series 90 output provided 
with modulating T775 models cannot drive 
electromechanical slidewire devices like 
older Series 3 mod motors (prior to series 6), 
V9055s, and S984s.
M24375
SENSORS  A, B, AND C (WHEN USED FOR TEMPERATURE SENSING)
 USE THE TWO TT CONNECTIONS AND ARE POLARITY INSENSITIVE.
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
SOURCE (24, 120, OR 240 VAC).
1
2
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
C
NO
NC
T  
T
+
 
–
+
 
–
SENSOR A
SENSOR B
KNOCKOUT A
DIGITAL INPUT
POWER 
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
POWER
24 VAC
OUTPUT
RELAY 1
KNOCKOUT C
KNOCKOUT E
1
OUTPUT
RELAY 3
KNOCKOUT B
T775 BUS
OUTPUT
RELAY 4
DIGITAL
OUTPUT
ALARM
2
T  
T
SENSOR C
T  
T
C
+
120
COM
240
Table 2. Description of Wiring Terminal Connections. 
Connection
Termina
l Description
Sensors
Sensor A
Sensor B
Sensor C
T T
T T
T T
Temperature Sensor; polarity insensitive:
A - This sensor can be the controlled 
temperature sensor
B - The control always uses this sensor 
for Reset only
C - This sensor can be used for 
differential and/or the controlled 
temperature sensor
Outputs
Relay 1
NO
COM
NC
120-240 Vac Relay Output
Relay 2
Relay 3
Relay 4
a
a
Relay 4 can be used for pump output. The pump output 
is always the last relay output.
DO Digital Alarm Output
Input
DI + - Digital Input (dry contact)
Interconnect
T775 BUS
+
 -
Terminal Connection to/from T775S
24 Vac Power
24V +
+
24 Vac Hot
Common
-
24 Vac Common
Ground
Earth Ground
b
b
A separate earth ground is required for all installations regardless of 
the power source (24, 120, or 240 Vac).
120 or 240 Vac Power
120 Vac 120 120 Vac Power
Common COM Common
240 Vac 240 240 Vac Power