INSTALLATION INSTRUCTIONS
® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved
95-7538—4
T7770A,B,C,D,E,F,G
Wall Modules
BEFORE INSTALLATION
Cover Disassembly
Two locking mechanisms are used on the cover of the wall
module. After installation, to disassemble the cover and the
subbase see Fig. 1.
Fig. 1. Cover disassembly.
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can
introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large inductive
loads such as motors line starters, lighting ballasts,
and large power distribution panels.
Shielded cable is required in installations where these
guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes
and ordinances or as specified on installation
wiring diagrams.
Wall module wiring can be sized from 14 to 22 AWG
(2.0 to 0.34 sq mm) depending on the application.
The maximum length of wire from a device to a wall
module is 1000 ft (305m).
Twisted pair wire is recommended for wire runs longer than
100 ft (30.5m).
The cover for the wall module is packed separately from
the subbase for ease of installation.
See Fig. 2 to release/replace the subbase terminal block.
Fig. 2. Releasing/replacing terminal block.
INSTALLATION
Mount the T7770A,B,C,D,E,F,G Wall Modules on an inside
wall approximately 54 in. (1372 mm) from the floor (or in the
specified location) to allow exposure to the average zone
temperature. Do not mount the wall modules on an outside
wall, on a wall containing waterpipes or near air ducts. Avoid
locations that are exposed to discharge air from registers or
radiation from lights, appliances, or the sun.
The wall modules can be mounted on a wall, on a standard
utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm
wall outlet box (see Fig. 3). When mounting directly on a wall,
use the type of screws appropriate for the wall material.
M11394
T7770E
BUTTON HEAD
SOCKET CAP
SCREW
ALLEN TOOL
STEP 1
STEP 2
STEP 3
70
65
60
55
75
auto
0
1
80
85
M17988
PRESS SHADED AREA
OF TAB WITH THUMB TO
RELEASE TERMINAL BLOCK
FOR EASIER WIRING
Question and Answer IconNeed help?

Do you have a question about the Honeywell T7770A and is the answer not in the manual?

Honeywell T7770A Specifications

General IconGeneral
BrandHoneywell
ModelT7770A
CategoryRacks & Stands
LanguageEnglish

Summary

Before Installation

Cover Disassembly

Two locking mechanisms are used on the cover of the wall module. After installation, to disassemble the cover and the subbase see Fig. 1.

Installation Instructions

General Installation Guidelines

Wall module wiring can be sized from 14 to 22 AWG. Twisted pair wire is recommended for wire runs longer than 100 ft.

Installation

Mount the T7770A,B,C,D,E,F,G Wall Modules on an inside wall approximately 54 in. from the floor.

Wiring Modules With a Removable Terminal Block

Wire the terminal blocks as follows: 1. For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.

Wiring Modules Without a Removable Terminal Block

Attach the wires as follows: 1. Connect controller sensor leads to the sensor screw terminals.