PRO TH2000DV/TH1000DV Series
7
69-2800EFS—01
Setup function Settings & options (factory default in bold)
5 Heating cycle rate
(CPH: cycles/hour)
TH2110DV, TH1110DV and
TH1100DV
5 For gas or oil furnaces of less than 90% efficiency
1 Forsteamorgravitysystems
3 Forhotwatersystems&furnacesofover90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
6 Auxiliary heat
cycle rate (CPH)
TH2210DV and TH1210DV
3 For hot water systems & furnaces of over 90%
efficiency
1 Forsteamorgravitysystems
5 Forgasoroilfurnacesoflessthan90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
9 Compressor
cycle rate (CPH)
3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5,or6CPH]
13 Early Start (TH2110DV
and TH2210DV)
1 On **See page 8
0 Off
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
1 Five-minute compressor off time (See page 8)
0 Nocompressorofftime
20 Clock display (TH2110DV
and TH2210DV)
0 12-hour display
1 24-hourdisplay
25 Lower temperature
range (TH1100DV only)
0 Standard range 40°F to 90°F (4.5°C to 32°C)
1 Lowerrange(forgaragemode)35°Fto90°F
(1.5°Cto32°C)
40 Restore program
schedule to default
(TH2110DV and
TH2210DV)
0 Off
1 On-programscheduledefaultsettingsarelistedinthe
operatingmanual
Installersetup
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressorprotectionisbypassedduringtesting.Topreventequipmentdamage,avoid
cyclingthecompressorquickly.
NOTE: Theoptionsbelowmaynotbeavailableinallmodels.