VisionPRO
TM
TH8000 Series
9
69-2693—01
ENGLISH
Setup functions Settings & Options (factory default in bold)
0500 Furnace lter
change reminder
0 Off
1 10-day run time (about 1 month)
2 30-dayruntime(about3months)
3 60-dayruntime(about6months)
4 90-dayruntime(about9months)
5 120-dayruntime(about1year)
6 365-dayruntime(about3years)
0510 Humidier pad
change reminder
0 Off
1 90calendardays
2 180calendardays
3 365calendardays
0520 UV lamp change
reminder
0 Off
1 365calendardays
0530 Adaptive Intelligent
Recovery™
1 On ** See page 11
0 Off
0540 Program periods 4 4 program periods (Wake, Leave, Return, Sleep)
2 2programperiods(Wake,Sleep)
0580 Compressor
protection
5 5 minute compressor off time ** See page 11
[Otheroptions:0,1,2,3or4-minuteofftime]
0600 Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Otheroptions:40-89°F(4.5°Cto32°C)]
0610 Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Otheroptions:51-99°F(10.5°Cto37°C)]
0640 Clock format 12 12-hour time (i.e., “3:30 pm”)
24 24-hourtime(i.e.,“15:30”)
0650 Extended fan
timer (heat)
0 Off
90 Fanrunsfor90secondsaftercallforheatends
0660 Extended fan
timer (cool)
0 Off
90 Fanrunsfor90secondsaftercallforcoolingends
0670 Keypad lock 0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fullylocked
0680 Heat temperature
control
2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Chooseifroomdoesnotreachsettemperature
0690 Cool temperature
control
2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Chooseifroomdoesnotreachsettemperature
0700 Temperature
display offset
0 Thermostat displays actual room temperature
[Otheroptions:-3,-2,-1,1,2,3°Foffset(-1.5°Cto1.5°C)
0710
RESET
0 No reset
1 Reset installer options & program schedule to factory
default (only date and time settings are retained)
Installer setup