EasyManua.ls Logo

HP EVA P6000 - Page 43

HP EVA P6000
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EVA P6000
Operating Temperature
50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft altitude (1.8° C/1,000 m)
Shipping Temperature
-40° to 150° F (-40° to 66° C)
Humidity
10% to 90% non-condensing
Shipping Humidity
5% to 90% non-condensing
Operating Vibration
Sine 5-10 Hz 0.020" (0.5mm) double amplitude displacement, 10-500 Hz 0.1g, Random 10-500Hz at 0.15
Grms
Non-operating Vibration
Sine 10-150 Hz 0.3g, Random 10-500 Hz at 0.5 Grms
Shipping Vibration
(packaged, on shock pallet)
Sine 5-150 Hz 0.5g, Random 0.86 Grms from 5-300 Hz, consisting of 5-100 Hz at 0.0059 g2/Hz and 100-
300 Hz at 0.000049 g2/Hz
Operating Shock
5g half-sine 10mSec
Non-operating Shock
8g half-sine 10mSec
Shipping Shock
(packaged, on shock pallet)
Horizontal: 10-deg incline at 1m/Sec, Vertical rotational edge 0.15m
Altitude
Up to 8,000 ft (2,400 m)
Air Quality
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or larger
Power Data
(North America/Europe/Japan)
maximum configuration
NOTE:
This power information is for a maximum configuration using the default 208 - 240 Volt single-phase PDUs. Other PDUs may
use different plugs, voltages, etc. For more information on PDU support, please see the following URL:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/pdu.html
AC plug type
(quantity 2)
North America - 3 wire NEMA No. L6-30P, 30 Amp (208 to 240V, 50-60Hz 30A)
Europe - 3 wire, 2 pole IEC 309, 30 amp, (220 to 240V 50Hz 32A)
NOTE:
For other voltages, including 3-phase or 100-127V, see the PDU information for plug types at:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/pdu.html
.
Number of phases
Single (3-phase PDUs are also available)
Rated current
17A @ 200V-240V AC, 60Hz total, 4.25 A per power cord (2 PDUs)
34A @ 100-127V AC, 60/50Hz, 8.5A per power cord (2 PDUs)
NOTE:
The current ratings are for a full 42U cabinet with default PDUs. Different PDUs have different
current/power ratings. The cabinet may be full of EVA and other equipment and actual current loads will
vary by configurations. For the individual EVA P6300/P6350 or EVA P6500/P6550 current loads, see the
table below.
Nominal Line Voltage
North America - 208V or 230V or 120V
Europe - 230V
Japan - 206V or 108V
Latin America - 208V or 240V
Range Line Voltage
187V to 256V or 90V to 127V
Line Frequency
North America 60 Hz, Europe 50 Hz, Japan 50 or 60 Hz, Latin America 60K or 50Hz
EVA P6000 Array Power, Heat and Current
QuickSpecs
HP EVA P6000 Storage
Technical Specifications
DA - 13904 Worldwide — Version 26 — September 30, 2013
Page 43