Figure 12. Power calculation for 20 HP DL380 G6 servers
The Power Advisor determines that a rack configuration of 20 DL380 G6 servers would require the
following:
• 5761.6 VA total apparent power (20 x 288.08 VA) that the power distribution components must
transfer
• 17887.2 total BTU/hr that will need to be removed by the cooling system
• 27.6 amperes total current (20 x 2.38 A) drawn by the 24 servers
• 5245 total watts dissipated by the equipment
14