WIRING
3
STEP 1 Connect 120 VAC Hot to terminal L1. Connect
120 VAC Neutral to terminal L2. Disconnect means and
overload protection as required (provided by others).
Select the Diagram that
Matches your System Configuration
on Pages 4, 5 or 6
STEP 2 Connect the burner circuit to B1-B2.
(B2 is neutral.)
WARNING
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
HydroStat 3250-Plus Instructions: HydroStat Instructions.8pg 11/14/13 3:43 PM Page 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HydroStat 3250-Plus and is the answer not in the manual?

HydroStat 3250-Plus Specifications

Power IconPower
input voltage120 VAC, 60 HZ
Operating Environment IconOperating Environment
operating range – low limitOff or 110°F (43°C) - 200°F (93°C)
operating range – high limit100°F (38°C) - 220°F (104°C)
operating range – differentialsAutomatic
Electrical IconElectrical
burner contacts7.4 FLA, 44.4 LRA@120 VAC
circulator contacts5.8 FLA, 34.8 LRA@120 VAC
thermostat heat anticipator setting0.2A