EasyManua.ls Logo

hyfire HFW-CEM-02 - User Manual

hyfire HFW-CEM-02
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
HFW-CEM-02
WIRELESS CONVENTIONAL SYSTEM
EXPANDER MODULE
Hyfire Wireless Fire Solutions Limited - Unit B12a, Holly Farm Business Park, Honiley,
Warwickshire, CV8 1NP - United Kingdom
www.hyfirewireless.com
Picture 1 - Device overview
Picture 3 - Breakable holes for cable entry
Picture 2 - Wall fixing screw holes, their distances
from each other and the maximum allowed screw
diameter
Picture 6 & 7 - Power supply unit example schemes
Picture 11 - Convention-
al line wiring (zone line
EOL resistor inside of
the device)
MAIN MONITORING
BACKUP MONITORING
Picture 8 - Power
supply monitoring
lines wiring
Picture 4 - An example of a
conventional - wireless
system
DEVICE WIRING - POWER SUPPLY
The conventional system expander module must be power
supplied either:
- directly by the control panel or
- from an external power source or
- from an external power source with a power backup unit.
Use the scheme at the right for connecting the power supply to
the device.
This terminal wiring scheme is always applied.
If you want to use an external power source with a power
backup unit, two additional modules terminal blocks come in
use: MAIN MONITORINGand BACKUP MONITORING”.
MAIN MONITORINGis a terminal that supervises the main
power supply of an external power supply unit.
BACKUP MONITORINGis a terminal that supervises the backup power supply of an external power supply unit.
Lets have two examples of power supply units:
MAIN MONITORINGand BACKUP MONITORINGlines will be connected to the module as in the following scheme:
DEVICE WIRING - CONVENTIONAL ZONE LINE
In order to connect this device to the conventional zone line, two types of schemes can be used, depending on the positioning of the expand-
er module on the line:
- the expander module is positioned at the beginning or in the middle of the zone line (conventional devices follow the device on the line or
are positioned before and after it); therefore the zone line EOL resistor must be fitted externally as is normally done, but not into the devices
terminal blocks:
- the expander module is positioned at the end of the zone line (all conventional devices are positioned before it); therefore the zone line
EOL resistor must be fitted to the devices terminals and not externally as normally is done.
Picture 10 - Convention-
al line wiring (zone line
EOL resistor outside of
the device)
info@hyfirewireless.co.uk L20-SGCWE-1400 (vA.5)
GENERAL DESCRIPTION
The wireless conventional system expander module is a device permitting to add a wireless sub-system to a conventional fire security
installation. This device is connected directly to the conventional control panel zone line and is actually part of it. This device allows wireless
sounders silencing by being controlled by the control panels sounder output line.
Note: The latest release of the wireless system configuration software is available from the manufacturers website.
WHAT TO CHECK BEFORE INSTALLATION
Before installing the conventional system expander module
check these following items:
- This device must be installed following your national and / or international codes of practice and standards: check them befo re performing
the installation of this device.
- This device is compatible with most of the conventional control panels; check that the control panel is equipped with a power supply output
through which you can, if desired, power the conventional system expander module; check if the panel is provided with a sounder output;
check that control panels specifications are suitable; for all this, consult your control panels documentation or consult your control panels
supplier for more information.
DEVICE POSITIONING FOR RADIO COMMUNICATION PERFORMANCE AND STABILITY
The conventional expander module must have a good radio communication with its wireless systems child devices. In order to achieve this,
before positioning it and installing it, apply scrupulously the following points:
- Avoid installing the module close to: · equipment using large amounts of electrical current
· large metal objects, structures or metal ceiling structures
· fluorescent lighting fixings
· computers, their cabling and network cabling.
- If there are other wireless translators or wireless modules, keep a distance between them of at least 2 meters. In general ev ery installed
radio device (child devices included) must have a minimum distance of at least 2 meters from each other.
- It is recommended to install the conventional expander at a height from the floor of at least 2 - 2.5 meters.
- Install the conventional expander perfectly flat on the wall.
- The conventional expander must be installed perfectly straight on the wall; this means that the antenna under the device must be perpen-
dicular to the floor and the antenna on the right of the device must be parallel to the floor.
Environmental parameters (temperature, humidity and so on) must be in the ranges specified in the conventional expanders technical
specifications, which can be found at the beginning of this manual; this point applies, obviously, to all other wireless devices.
- After having installed the conventional expander, make sure that its child devices (sensors, call points, etc.) are reached by a good, strong
signal (refer to the single devices manuals) in their position of installation.
Radio transmission ranges for the conventional expander can found in the technical specifications at the beginning of this manual.
- Use the personal computers Wirelex-fire software for configuring and administering the system.
PLACEMENT AND FIXING
The conventional system expander modules lodgement box is designed with four 20 mm breakable, knock-outentry holes (two at the top
and two on the upper side of the rear of the box), allowing sealed, cable gland fitted, cables to be connected to the device.
To place and fix the module perform in sequence the following steps:
- Find a suitable location for the devices box.
- Prepare the cable openings on the box.
- Securely and adequately fix the devices box to the wall with adequate screws.
- Fit the cables gland (or glands) into the knocked outdevice boxs cable entry; check glands IP rating: it must be equal or greater than the
IP rating of the expander module: see the TECHNICAL SPECIFICATIONS table.
- Feed the cables into the box, giving them sufficient length for a secure connection.
WIRING CONNECTIONS
The conventional system expander modules wiring phase of the installation has the following objectives:
- Connect the power supply cables (either from the control panel of from an independent source).
- Connect main and backup power supply monitoring inputs (optional).
- Connect the conventional zone line.
- Connect the control panels sounder output (optional).
- Install the end of line (EOL) resistors required as specified in this manual; their values must be chosen according to the control panels
specification and literature.
WIRING WARNINGS
Three warnings about wiring:
- Perform any wiring operation with the power supply source and the control panel inactive.
- Electrostatic sensitive device: observe precautions when handling and making connections.
- Connections to the terminals are polarity sensitive, thus, please, check them by referring to the wiring instructions of this manual.
IMPORTANT NOTE
Check and apply the ZONE ALARM EOLand the CHECKING THE POSITIONING OF THE ELECTICAL BRIDGESparagraphs before
using the expander module.
928r/01
TECHNICAL SPECIFICATIONS *
Communication range between expander and
wireless devices
200 meters (in open space)
Operating frequency 868.15 MHz 869.85 Mhz
Modulation type FSK
Operating frequency channels 7
Radiated power 5 dBm (3 mW)
Power supply voltage range **
9 VDC - 30 VDC
12 VDC typical
Power supply lower fault threshold 9 VDC
Conventional zone line applied voltage
Same as devices power
supply applied voltage
Sounders line maximum voltage 27 VDC
Expander maximum current consumption 60 mA at 12 VDC (alarm)
Operating temperature range -30 °C to +50 °C
Dimensions (without antennas) 120 mm x 160 mm x 51 mm
Weight 330 grams
Ingress protection rating IP 51C
Required programming software
Wirelex-Firerevision 5.0
and successive
-
+
POWER SUPPLY
Picture 5 - Power
supply connection
scheme
96 mm
146 mm
4 mm
* Check latest version of document TDS-SGCWE for further data, obtainable
from your supplier.
Picture 9 - Ferrite
ring installation
WARNING!
POWER SUPPLY -AND POWER SUPPLY +” WIRES MUST PASS INTO
THE SUPPLIED FERRITE RING.
IMPORTANT: Please note that with this wiring
arrangement, if a fault occurs on the wireless
sub-system, the remaining conventional zone
after the expander may be isolated until the
fault has been cleared. This will apply unless
each detector on the circuit is equipped with a
Schottky diode that the panel can use for
continuity purposes.
Please refer to your applicable codes of prac-
tice and to your conventional control panel
documentation.
* * Power source type ES1, PS2
Question and Answer IconNeed help?

Do you have a question about the hyfire HFW-CEM-02 and is the answer not in the manual?

Summary

General Description and Installation

Technical Specifications

Details the communication range, frequency, power, operating conditions, and physical properties of the expander module.

Pre-Installation Checks

Lists essential items to verify before installing the wireless system expander module.

Positioning for Radio Performance

Guidance on optimal placement to ensure good radio communication with wireless devices.

Placement and Fixing

Instructions on how to prepare and securely fix the expander module's housing to a wall.

Wiring Connections Overview

Outlines the objectives for connecting power supply, zone lines, and sounder outputs.

Wiring Warnings

Critical safety and handling precautions for wiring operations.

Device Wiring Details

Power Supply Wiring

Details on connecting the power supply, including optional backup monitoring.

Conventional Zone Line Wiring

Explains how to connect the expander module to the conventional zone line.

Control Panel Sounder Output Line Wiring

Instructions for connecting the module to the control panel's sounder output line.

Zone Alarm EOL Installation

Guidance on installing the zone alarm end-of-line resistor.

Electrical Bridges Positioning

Information on the correct positioning of electrical bridges on the PCB for operation.

System Operation and Testing

Visual LED Indicator

Explanation of the device's LED signals for power supply status.

Programming the Wireless Sub-System

How to create and program the wireless sub-system using dedicated software.

System Testing Procedure

Steps for testing the wireless conventional system expander module's functionality.

Sealing the Device with its Cover

Instructions for securely closing the device after testing.

Warnings and Limitations

hyfire HFW-CEM-02 Specifications

General IconGeneral
Power Supply24V DC
Operating Temperature-10°C to +50°C
IP RatingIP30
Relative Humidity0% to 95% (non-condensing)
Device TypeLoop Extender
Maximum Loop Length2000m