WIFI fan coil unit thermostat manual
Search for "Smart RM" or
Smart Life
Download the Wifi App from Google Play or
APP Store
Turn on the thermostat, press and hold
the key combination and
Activate WIFI distribution network icon
Technical data
Voltage: AC90~230VAC 50/60Hz Output
On/off type
Current: 3A Display temperature range
0~55°C
Accuracy: ±0.5ºC Work environment:
0~50°C
Setting range: 5ºC - 35ºC Size
86 * 86mm
Sensor:
NTC(10k)1%
Button
Icon
Description
Increase key: short press to adjust data,long press to display external senor temperature
(When the sensor type is N3 in the advanced option)
Mode switching key: short press to switch between manual mode and program mode,
long press to set special function parameters
Decrease keyshort press to adjust data, long press to lock/unlock keys
Fan speed selection key: short press to set fan speed (confirm key when setting
parameters), long press to enter sleep function setting
Power key
Press them together to enter matching wifi mode
WIFI connection, flashing as EZ wifi pair mode
Wifi status: Disconnection Child lock
cloud icon ,if flashing ,then enter AP wifi pair mode
Program mode;run preset program Manual mode
Temporary manual mode Clock
Holiday mode, Holiday days and temperature can be set to run in countdown mode
Operation
Operation
Description
Fan Speed
Power on state ,press to choose fan speed high mid
low )、(Auto: animation)
Setting time
Power on state, press 3-5s chose 02 then press to set time
Minutemmflashingpress or to adjustpress to next setting.as
same method to set hour and week.finally press or wait 5S to exit
Timer
After connected wifi ,click
cloud
on the right corner of APP to set
Working mode
Power on state,long press 3-5S, short press " to choose 01,next press
to choose mode:
is mean cooling mode, is mean heating mode, is mean
ventilation mode is mean auto mode
Control valve
When cooling mode(heating mode),indoor temperature morelower) 1 than
setting temperature, open valve; after equal, closed valve,fan is still running.
Ventilation modefan is not control by temperature as default
If fan be controlled by temperature,then valve and fan will be closed.
Locked
function
long press to lock/unlock keys
Alarm
E1 internal sensor error
E2 external sensor error
Sleep mode
Power on state, long press , is flashing, short press to run itshort
press to cancel
RemarkSleep mode is not available when run ventilate mode or auto mode
Manual/
program mode
Power on state, short press to switch manual mode/program mode
Program mode setting
Thermostat support set different time and different temperatureCompatible with 5+2,6+1,7days
Program mode type
Question and Answer IconNeed help?

Do you have a question about the HYSEN HY08AC and is the answer not in the manual?

Summary

Thermostat Operation

Fan Speed Control

Select fan speed from high, mid, low, or auto modes.

Setting Time

Set the time by adjusting hour, minute, and week.

Timer Function

Activate timer function after connecting to cloud via APP.

Working Mode Selection

Choose between cooling, heating, ventilation, or auto modes.

Control Valve Operation

Valve opens when temp is lower than setting, closes when equal.

Locked Function

Long press to lock or unlock the thermostat keys.

Alarm Codes

E1 for internal sensor error, E2 for external sensor error.

Sleep Mode

Activate sleep mode, not available in ventilate or auto mode.

Manual vs. Program Mode

Switch between manual and program modes.

Program Mode Setting

Set different times and temperatures for program modes.

Button and Icon Functions

Key Button Functions

Short press for data adjust, long press for sensor temp or key lock.

Mode Switching Key

Switch modes or set special function parameters.

Fan Speed Key

Set fan speed or enter sleep function setting.

Power Key

Power on/off and enter matching Wi-Fi mode.

Wi-Fi Status Indicators

Indicates Wi-Fi connection status, EZ or AP pair mode.

Program and Temporary Modes

Run preset programs or enter temporary manual mode.

Child Lock and Clock

Enable child lock and set the clock function.

Advanced Options

Temperature Calibration

Adjust temperature calibration by -9 to +9°C.

Children Lock Settings

Configure half lock or full lock for children.

Limit Temperature Settings

Set the lowest and highest limit temperatures for operation.

Fan Energy Saving Control

Control fan behavior based on valve status.

Program Mode Type Configuration

Select program mode type: 5+2, 6+1, or 7-day.

Valve Output Selection

Choose between 2-pipe or 4-pipe valve output.

Sensor Type Configuration

Select internal, external, or double sensor type.

External Sensor Temperature Setting

Set temperature for the external sensor.

Standby Brightness

Adjust display brightness for standby mode.

Logo Display on Standby

Enable or disable logo display during standby.

Reset Function

Reset the thermostat to factory default settings.

Installation and Safety

Cautions on Installation

Important notes to prevent display fluctuations and ensure proper installation.

Installation Diagram

Step-by-step visual guide for installing the thermostat.

Overview

This document describes a WIFI fan coil unit thermostat, providing details on its functions, technical specifications, usage, and installation.

Function Description

The thermostat is designed to control fan coil units, offering various modes for temperature regulation and fan speed. It supports both cooling and heating modes, as well as ventilation. The device can be controlled manually or through a programmed schedule, and it integrates with a WIFI app for remote management.

Key Features:

  • Temperature Control: Maintains desired indoor temperature by controlling the fan and valve.
  • Fan Speed Selection: Allows users to choose between high, mid, low, and auto fan speeds.
  • Programmable Schedule: Supports 5+2, 6+1, and 7-day programming modes, enabling different time and temperature settings for various days of the week.
  • WIFI Connectivity: Connects to a WIFI network for remote control via "Smart RM" or "Smart Life" apps.
  • Child Lock: Prevents unauthorized changes to settings with half-lock (temperature and on/off adjustable) and full-lock options.
  • Sleep Mode: Reduces energy consumption by running the fan at a lower speed for a set period.
  • Energy Saving Control: Offers options to turn off the fan when the valve is off or keep it always on.
  • External Sensor Support: Can utilize an external sensor for temperature detection, particularly useful in heating scenarios where the valve opens and the fan turns on based on external temperature thresholds.
  • Holiday Mode: Allows setting specific days and temperatures for holiday periods, running in a countdown mode.
  • Alarm Function: Displays error codes (E1 for internal sensor error, E2 for external sensor error) to indicate issues.
  • Display Logo Control: Option to display or hide the logo on standby.
  • Reset Function: Resets the thermostat to factory defaults.

Important Technical Specifications

  • Voltage: AC90~230VAC 50/60Hz
  • Output: On/off type
  • Current: 3A
  • Accuracy: ±0.5°C
  • Setting Range: 5°C - 35°C
  • Display Temperature Range: 0~55°C
  • Work Environment: 0~50°C
  • Size: 86*86mm
  • Sensor: NTC(10k)1%
  • Valve Output Options: 2-pipe or 4-pipe systems.
  • Sensor Type Options: Internal sensor (N1), external sensor (N2), or double sensor (N3).

Usage Features

Basic Operation:

  • Power On/Off: Controlled by the power key.
  • Fan Speed Selection: Short press the fan speed key to cycle through high, mid, low, and auto.
  • Mode Switching: Short press the mode key to switch between manual and program modes. Long press to set special function parameters.
  • Temperature Adjustment: Use the increase/decrease keys to adjust the set temperature.
  • Time Setting: Long press the clock key for 3-5 seconds, then short press to choose "02". Use increase/decrease keys to adjust minute, hour, and week.
  • WIFI Pairing: Press the increase and fan speed keys together to enter WIFI matching mode (flashing icon).
  • Child Lock Activation: Long press the decrease key to lock/unlock keys.
  • Sleep Mode Activation: Long press the fan speed key.

Program Mode Setting:

  1. Long press the mode key for 3-5 seconds.
  2. Short press the mode key to choose "03".
  3. Short press the mode key again to enter program mode setting.
  4. Use the increase/decrease keys to adjust values for time sections and temperatures.
  5. Short press the mode key to move to the next time section setting.

Advanced Options (Accessed by turning off the thermostat, then long pressing the mode key for 5 seconds):

  • A1 Temperature Calibration: Adjusts temperature reading from -9°C to +9°C (default -1°C).
  • A2 Children Lock: 0: half lock, 1: full lock (default 0).
  • A3 Setting the lowest limit temperature: 5-15°C (default 5°C).
  • A4 Setting the highest limit temperature: 16-50°C (default 35°C).
  • A5 Fan energy saving control: 0: fan off when valve off, 1: fan always on when valve off (default 0).
  • A6 Program mode type: 0=5+2, 1=6+1, 2=7 (everyday all the same) (default 0).
  • A7 Choose valve output: 2:2pipe, 4:4pipe (default 4).
  • A8 Sensor type: N1:internal sensor, N2:external sensor, N3:double sensor (default N1).
  • A9 Set temperature for external sensor: 20-60°C (default 38°C).
  • AA Standby bright: 0: off, 1: weak bright, 2: brighter (default 1).
  • AB LOGO display on standby: 0: No display, 1: Display (default 1).
  • AC Reset: Resets to factory defaults.

Maintenance Features

Installation Guidelines:

  • Placement: Install the thermostat approximately 1.5m above the ground. Avoid wall corners, door/window sides, behind doors, unheated areas, or near hot/cold air ducts, radiators, flues, or thermal pipes to ensure accurate temperature readings.
  • Power Supply: Ensure the power cable is well insulated during installation.
  • Internal Circuit Board: Do not open the internal circuit board.
  • Mounting: Designed for standard 75x75x35mm wall mount boxes. Follow instructions to open the rear cover base, mount it, and wire it.
  • Safety: Disconnect the system power before installation. The maximum AC voltage should not exceed 250V.

Cautions:

  • The thermostat may not immediately display sudden temperature changes due to programming designed to prevent high fluctuations.
  • Error codes E1 (internal sensor error) and E2 (external sensor error) indicate potential issues requiring attention.

HYSEN HY08AC Specifications

General IconGeneral
BrandHYSEN
ModelHY08AC
CategoryThermostat
LanguageEnglish