HYSEN HY607
2 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Turn on thermostat,long press it for 3-5seconds to holiday mode setting. Appear
OFF, press or change to ON,then press to confirm opening holiday mode
4 Turn off thermostat ,long press
to enter into advanced B setting
B
1 Decrease key
2 Long press to lock /unlock
D
1 Increase key :
2 Long press to inquire external sensor temperature
3 In the Auto model, press or enter to temporary manual mode
Programmable
5+2 (factory default),6+1 and 7 models 6 times period setting for user choose. In the advanced options
choose model of you need, under power on state, long press for 3-5 seconds enter into programming
mode setting, then short press choose: hour,minute, time period, and press and to adjust
data, finished setting, about 10 seconds will automatic save and exist.
6
Sleep
600
20
800
15
1130
15
1330
15
1700
15
2200
15
The optimum comfort temperature is 18-22.
Advanced options A
Under turn off state, long press for 3-5 seconds to access advanced A setting.
From A1 to AE, short press to choose the option, and adjust data by , , short press to switch
next option.Remain about 5 seconds after finish setting will quit setting.
NO
Setting Options
Data Setting Function
Factory Default
A1
Measure Temperature
Calibration
-9-+9
0.5 Accuracy
Calibration
A2
Temperature control
return difference setting
0.5-2.5
1
A3
Children lock setting
0:half lock 1:full lock
0
A4
Power with memory
function
0:Power with memory function
1:Shutdown power after power off
2:Shutdown power after power on
0
A5
Backlight sleep brightness
0: 0% of brightness
1: 50% of brightness
2: 100% of brightness
1
A6
Weekly programming
selection
0: 5+2 1:6+1 2 :7
0
A7
Setting temperature
lowest limit
1-10
5
A8
Setting temperature
highest Limit
20-70
35
A9
Protection of low
temperature
1 :1-10
2:Exceed 10, screen display--, Low
temperature protection was cancelled.
5
AA
Protection of high
temperature
1::35-70
2: low than 35 , screen display -- ,high
temperature protection was canceled
45
AB
Return different for high
temperature protection
1-9
2
AC
Running temperature of
open window function
1:10-20
2: low 10,screen display --,open window
function was canceled
15
AD
Running time of open
window function
10-20 min
10
AE
Reset
Long press until whole display
Advanced options B
Under turn off state, long press for 3-5 seconds to access advanced B setting
NO.
Setting Options
Data Setting Function
Factory Default
BN
Choose sensor
N1: only inner sensor
N2: only external sensor
N3: both sensor
N1
BC
Descaling function
0: closed 1: open
0
BO
version
V1.0
1.0
Return difference : limit valve of external sensor is 45 for factory default (A6),value of external
sensor control return difference (A3) is 2. when temperature rise to 45,then relay stop working and will
remind high temperature production alarm. If temperature decline to 43relay continue to work and
heating alarm will be relieved. (it can be operated ,only when indoor temperature is lower than setting
temperature )
Sensor fault display:please choose correct working way of built-in and external sensor, if choose
wrongly or sensor fault (breakdown), E1 or E2 will be displayed on the screen. Thermostat will stop
heating until the fault is eliminated