5-7
TROUBLESHOOTING
SFC BOILER / WATER HEATERS - SFC 199
F007 No or insufcient ame current.
Check the ignitor.
Check the wiring of the ignitor for breakage.
Replace the ignitor.
F008 Incorrect fan speed
Check the fan cable.
Check and/or replace the fan.
Replace the controller.
F009 Internal fault in burner
controller.
Replace the controller.
F010, F011 Sensor fault S0.
Check the wiring of heat exchanger sensor S0 for
breakage.
Check whether the heat exchanger sensor S0 is
connected correctly.
Check for the correct operation of heat exchanger
sensor S0.
Replace the heat exchanger sensor S0.
F012 Sensor fault S5.
Check the wiring of ue gas sensor S5 for breakage/
shutdown.
Check whether the ue gas sensor S5 is connected
correctly.
Check for the correct operation of ue gas sensor S5.
Replace the ue gas sensor S5.
F014 Mounting fault sensor S0.
Heat exchanger sensor S0 is not mounted correctly.
Mount the sensor correctly.
F016 Mounting fault S3
Domestic hot water sensor S3 is not mounted
correctly. Mount the sensor correctly.
F018 Flue and/or air supply
duct is blocked.
Check the ue and the air supply duct.
Clean the ue and/or the air supply duct.
F019 Boiler Memory Module (BMM) fault.
Check BMM wiring for breakage.
Replace the BMM.
F027 Short circuit of outdoor
sensor S6.
Check the wiring of the outdoor sensor for breakage.
Replace the outdoor sensor.
F028 Reset error.
Check the reset button for unintentional operation (e.g.
cleaning of the control panel).
Replace the burner controller.
F029 Gas valve fault.
Check the gas valve for leakage.
Replace the controller.
F030 Sensor fault S3.
Check the wiring of the domestic hot water sensor S3
for breakage.
Check whether the domestic hot water sensor S3 is
connected correctly.
Check for the correct operation of domestic hot water
sensor S3.
Replace the domestic hot water sensor S3.