MAP 0300 (continued)
031 (continued)
Check that the MAE is not running the quick configuration. Look at the MAE MOS
Console, and check if the following is displayed:
Config only>
Is Config only> displayed?
Yes No
032
The SAC card is defective. Replace it. See Chapter 4, “Multiaccess
Enclosure FRU Exchange” on page 4-1.
Restart the verification procedure. Go to Step 001 on page 3-6.
033
Wait for the end of configuration, then restart the problem determination.
034
You are at this Step because the ac indicator on a power supply is OFF.
Check that the ac power cable of the suspected unit is well connect at:
The font of the unit
On the ac outlet distribution box.
Is the problem solved?
Yes No
035
Continue with Step 037.
036
Problem solved. Go to “CE Leaving Procedure” on page 5-60.
037
3-12 3746-9X0: MAE Installation and Maintenance