Table 48. Dimensions
Maximum configuration
weight
1
Height Width Depth
403 kg (885 lb) 1800 mm (71.0 in.) 650 mm (25.5 in.) 1020 mm (40.0 in.)
1
Side and top clearances are optional when operating.
Table 49. Electrical
Electrical characteristics Properties
kVA (maximum) 0.789
Rated voltage and frequency 100 - 127 or 200 - 240 V ac at 50 - 60 plus or minus 0.5
Hz
Thermal output (maximum) 2560 Btu/hr
Power requirements (maximum) 750 W
Power factor 0.95
Inrush current 41 A
Leakage current (maximum) 3.5 mA
Phase 1
Table 50. Temperature requirements
Operating Nonoperating
10 - 38°C (50 - 100.4°F) 1 - 60°C (33.8 - 140°F)
Table 51. Environment requirements
Environment Operating Nonoperating
Wet bulb temperature 23°C (73.4°F) 27°C (80.6°F)
Figure 14. Model 0551 and 9406-270 rack