Table 129. Supported PDU power cords for POWER8 systems
Feature
code
(FC)
Description
v Voltage
v Amperage
v Phase
v Length
v Wall plug
IBM
shipped
plug
View of
plug
Matched
female
connector
(on cord)
Matched
female wall
receptacle
(on wall)
IBM part
number
Countries
6489 Power cord, PDU to
wall
v 230 V ac output
v 32 A
v 3 phase wye
v 4.3 m (14 ft)
v IEC 309, 3P+N+G
Plug type
532P6W
Connector
type
532C6W
Receptacle
type
532R6W
39M5413 Europe,
Middle East,
Africa
(EMEA)
6491 Power cord, PDU to
wall
v 230 V ac
v 63 A
v Single phase
v 4.3 m (14 ft)
v IEC 309, P+N+G
Plug type
363P6W
Connector
type
363C6W
Receptacle
type
363R6W
39M5415 Europe,
Middle East,
Africa
(EMEA)
6492 Power cord, PDU to
wall
v 200 - 208 V ac or 240
V ac
v 60 A plug (48 A
derated)
v Single phase
v 4.3 m (14 ft)
v IEC 309, 2P+G
Plug type
360P6W
Connector
type
360C6W
Receptacle
type
360R6W
39M5417 United
States,
Canada,
Latin
America,
Japan, and
Taiwan
6653 Power cord, PDU to
wall
v 230 V ac output
v 16 A
v 3 phase wye
v 4.3 m (14 ft)
v IEC 309, 3P+N+G
Plug type
516P6W
Connector
type
516C6W
Receptacle
type
516R6W
39M5412 Switzerland
6654 Power cord, PDU to
wall
v 200 - 208 V ac or 240
V ac
v 30 A plug (24 A
derated)
v Single phase
v 4.3 m (14 ft)
v NEMA L6-30
Plug type
NEMA
L6-30P
Receptacle
type NEMA
L6-30R
39M5416 United
States,
Canada,
Latin
America,
Japan, and
Taiwan
106 Site and hardware planning