4
Rev. 2
Preservation Instructions
Unpacking Inspection
Caution: It is recommended using gloves and protective eyewear when unpacking
Verify product is as identified on the packing list. Air conditioner should arrive banded to pallet in the
proper upright position. See arrows on packaging for verification. Any evidence of damage should be noted
on the freight bill. The freight carriers claim procedure should be followed. Ice Qube cannot accept
responsibility for damages that occur during shipping. If the shipping container was damaged or marred
in any way, check for scratches, dents, loose hardware, presence of oil or any other irregularities with the
Ice Qube TMS.
Package Contents
Included in the shipment with the air conditioner will be:
1. Operation manual
2. Mounting hardware
3. Condenser air diverter plate
4. Standard master warranty
5. Ethernet controller manual (Optional)
6. Enclosure gasket
Handling
Ice Qube recommends that the unit remains in the proper upright position, as indicated on the shipping
container. The unit must remain upright for a minimum of 24 hours before initial operation to ensure oil
has returned to the compressor. Operation before the 24-hour time may cause compressor damage and
shorten the life of the system. Operation before this 24-hour period will void all warranties.
Storage
The storage space temperature should be in the range of -40 to 85°C (-40 to 185°F) in a non-condensing
environment.
CONDITIONS OF ACCEPTABILITY: When installed in the end use equipment, the following
considerations are to be examined:
1. The maximum operating temperature of the devices while subjected to the temperature test at a 60°C
ambient air temperature is in accordance with the temperature class of the below table:
With Crankcase Heater Option
Maximum Temperature T-Code Unit
100°C T5 IQ1-2-3000EV
200°C T3 IQ4-5-6-8-10-12000EV
135°C T4 IQ14-17-20000EV
Without Crankcase Heater Option
Maximum Temperature T-Code Unit
85°C T6 IQ1-2-3000EV
135°C T4 IQ4-5-6-8-10-12000EV
100°C T5 IQ14-17-20000EV
2. The subject devices must be used within their Recognized “Ratings” and conditions of acceptability as
referenced in the User’s Manual.
3. Consideration is to be given to the Conditions of Acceptability specified in the individual recognitions
when these components are employed in the end-use equipment