Condensate Section
Has water been placed in drain pan to conrm proper drainage? Yes No
Are correct lters in place? Yes No
Refrigerant Piping
If leaks are found, report any leaks to ICE Warranty Service Dept.
C. Check Rated Voltage at Terminal Block for Imbalance before starting of Unit.
208/230V 1 Phase 208/230V 3 Phase 460V 3 Phase
380V 3 Phase 50Hz. 575 3 Phase 60 Hz.
Measured Line to Line Volts L1&L2_______V. L1&L3 ________V. L2&L3______V.
(L1&L2 + L1&L3 + L2&L3)/3 = Avg. Voltage = _______________
Max. Deviation from avg. voltage = ______________volts
Voltage imbalance = (100 x Max. Deviation)/avg. Voltage = ___________%
A voltage deviation greater than 2% with the unit running should be addressed and corrected. Excess
voltage deviation can cause the compressor to overheat and to operate inefciently.
Example: Maximum Deviation from Average Voltage X 100 (for Percent)
Average voltage
Measured Voltages:
L1 & L2 = 241 Volts
L1 & L3 = 243 Volts = 717 / 3 = 239 Average Voltage
L2 & L3 = 233 Volts
239 - 233 = 6
239 X 100=2.5% Voltage Unbalance
Three phase units only check fan & compressor rotation.