EasyManuals Logo

ICP F9MVE0601714A2 User Manual

ICP F9MVE0601714A2
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace: (F/G)9MVE
Specifications subject to change without notice.
440 04 4801 00 7
Adjust Manifold Pressure
1. Adjust manifold pressure to obtain low fire input rate.
(See Figure 3)
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device
to manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1—2 on furnace control to ON
position to lock furnace in lowheat operation. (See
Figure 4 and Figure 5)
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on
control to start furnace. (See Figure 4)
h. Remove regulator adjustment cap from low heat gas
valve pressure regulator (See Figure 3) and turn
lowheat adjusting screw (3/16 or smaller flattipped
screwdriver) counterclockwise (out) to decrease input
rate or clockwise (in) to increase input rate.
NOTICE
DO NOT set lowheat manifold pressure less than 1.3in. w.c.
(324 Pa) or more than 1.7in. w.c. (423 Pa) for natural gas. If
manifold pressure is outside this range, change main burner
orifices.
i. Install lowheat regulator adjustment cap.
j. Reinstall manifold pressure tap plug from gas valve.
k. Move setup switch SW12 to OFF position after
completing lowheat adjustment.
l. Leave manometer or similar device connected and
proceed to Step 2.
2. Adjust manifold pressure to obtain high fire input rate.
(See Figure 3)
a. Jumper R to W/W1 and W2 thermostat connections
on furnace control. This keeps furnace locked in
highheat operation.
b. Remove regulator adjustment cap from highheat
gas valve pressure regulator (See Figure 3) and turn
high heat adjusting screw (3/16in. or smaller
flattipped screwdriver) counterclockwise (out) to
decrease input rate or clockwise (in) to increase input
rate.
Figure 3
Redundant Automatic Gas Control
Valve (2Stage)
ON/OFF Switch
Regulator Seal Cap
Regulator Adjustment
Regulator Seal Cap under Cap
1/2” NPT Outlet
1/8” NPT Manifold
Pressure Tap
1/8” NPT Inlet
Pressure Tap
1/2” NPT Inlet
A11152
NOTICE
DO NOT set highheat manifold pressure less than 3.2in. w.c.
(797 Pa) or more than 3.8 in. w.c. (947 Pa) for natural gas. If
required manifold pressure is outside this range, change main
burner orifices to obtain manifold pressure in this range.
c. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main
burner flame should be clear blue, almost
transparent. (See Figure 14)
d. Reinstall manifold pressure tap plug to gas valve.
e. Remove jumpers R to W/W1 and R to W2.
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to
prevent gas leak.
!
WARNING
3. Verify natural gas input rate by clocking meter.
NOTE: Contact your HVAC distributor or gas supplier for metric
gas meter Tables, if required.
a. Turn off all other gas appliances and pilots served by
the meter.
b. Move setup switch SW12 to ON position. This
keeps furnace locked in lowheat operation when
only W/W1 is energized.
c. Jumper R to W/W1.
d. Run furnace for 3 minutes in lowheat operation.
e. Measure time (in sec) for gas meter to complete 1
revolution and note reading. The 2 or 5 cubic feet dial
provides a more accurate measurement of gas flow.
f. Refer to Table 2 for cubic ft. of gas per hr.
g. Multiply gas rate cu ft./hr by heating value (Btuh/cu
ft.) to obtain input.
h. If clocked rate does not match required input from
Step 1, increase manifold pressure to increase input
or decrease manifold pressure to decrease input.
Repeat steps b through e until correct lowheat input
is achieved. Reinstall low heat regulator seal cap on
gas valve.
i. Jumper R to W/W1, and W2. This keeps furnace
locked in highheat operation when both W/W1 and
W2 are energized.
j. Repeat items (d) through (h) for highheat operation,
repeating Step 2 and adjusting the highheat regular
screw, as required.
4. Restore furnace to normal operating condition.
a. Turn gas valve On/Off switch to OFF.
b. Remove water column manometer or similar device
from manifold pressure tap.
c. Replace manifold pressure tap plug to gas valve.
d. Turn gas valve On/Off switch to ON.
e. Move setup SW12 on furnace control to position
required for attached thermostat (OFF for
singlestage thermostats, ON for twostage
thermostats).
f. Check for gas leaks and verify furnace operation.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICP F9MVE0601714A2 and is the answer not in the manual?

ICP F9MVE0601714A2 Specifications

General IconGeneral
BrandICP
ModelF9MVE0601714A2
CategoryFurnace
LanguageEnglish

Related product manuals