BL3x-MT-EN-08 page 21/59
Reader B Hold Check why the Reader B command is being sustained on the
control board connector block
Position Fail The type of sensor selected is “Analogue Sensor” (“QUICK
START menu “Positioning"); nevertheless, the obstacle still
has to be activated (Activate Motor?” OK).
Counter CR
The reader counter (see the “OPTIONS” menu X
“Counter CR”) is greater than zero.
Or the timing for no passage is other than zero (see
the "TIMING" menu X "No Passage").
Open Status Cases when the obstacle is prevented from opening during a
request to open.
OK Normal opening.
Lock CL Hold Check why the Lock CL command is being sustained on the
control board connector block.
Lock Close LCD The Test Mode” parameter of the “TEST” menu is not set to
Deactivated”.
Delay Befor OP Wait for the time programmed under the “Delay Bef. OP under
the “TIMING” menu to elapse.
Stop Cmd Hold
Check why the close order is being sustained on the
control board connector block.
Check whether the “Stop CMD" parameter is
programmed correctly (“Options” menu).
Arm ELV Locked
Check whether the detector of the unlocking of the
electrically locking (ELV) tip is functioning properly.
Check whether the “Arm" parameter in the
“OPTIONS” menu is programmed correctly.
Arm ELV Detect
Check whether the detector sensing the presence of the
arm is functioning properly on the control board connector
block.
Position Fail The type of sensor selected is “Analog. Sensor” (“QUICK
START” menu Positioning"); nevertheless, the obstacle still
has to be activated (Activate Motor?” OK).
Counter 1 0 to 99,000,000
(0 by default)
Total number of manoeuvres executed by the obstacle since it
was first put into service.
Counter 2 0 to 99,000,000
(0 by default)
Representation of counter 1, with the possibility of resetting it to
zero.
Reset counter 2 Counter 2 reset to zero.
OFF (by default) No resetting.
ON Request to reset to zero.
Done Message is displayed for 1 second when the counter has been
reset to zero.