IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
85
>
13.1.10 Electrical connection
33806
Voltage supply IN X31
Plug and socket connection
M12
Wiring
1:
+ 24 V DC (US)
2:
-
3:
GND (US)
4:
-
Ethernet IN / OUT X21, X22
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
IoT X23
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
Process connection IO-Link ports Class A X01...X04
Plug and socket connection
M12
Wiring
1:
Sensor supply (US) L+
2:
DI
3:
Sensor supply (US) L-
4:
C/Q IO-Link