EasyManua.ls Logo

Imer Group KOINE 3 - Page 30

Imer Group KOINE 3
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
IMER INTERNATIONAL S.p.A.
KOINE 3
INCONVENIENTI CAUSE RIMEDI
Machine does not start Water
Water pressure too low: the gauge shows pressure below 2 bar
(green lamp on?), the display shows the text H
2
O
- Check that water is delivered from the supply
hose
- Check that the water lter is clean
- Check that the water pump is switched on
- If the pump collects from a tank, check that it has
been primed and there are
no leaks from couplings
Machine does not start Material
- Product too dry in mixing chamber
(mortar pump seized? red lamp on?)
- Initial start-up not performed correctly (see
para.11)
- Water ow rate setting too low (see para.11)
- No water delivered to mixing chamber
(water inlet obstructed, water solenoid valve
malfunction)
Machine does not start Grid
-Grid not inserted completely, the display shows the text Bloc
-Check that the grid is positioned correctly
Machine does not start Air
- The air pressure, with jet valve completely open, does not fall
below the minimum pressure value on the machine pressure switch
(table 1)
- Check that the air hose is not bent or obstructe-
do
- Check that the jet nozzle is perfectly clean
Machine does not start
and compressor does
not start and the blue
light is OFF
Electrical current
- No current delivered to connector of site panel
(fuses?)
- No power delivered to machine
(defective connector connection? loose cable?)
- Main switch not ON
- Check points listed alongside
Machine does not start
but compressor starts
Electrical current
- Start selector switch not in correct position
- Mixing chamber open
(start/stop pushbutton lamp on?)
- Mortar pump motor connector not inserted
(start/stop pushbutton lamp on?)
- Low water pressure switch trips on start-up
(water pump switched on ?see also "machine does not start due to
water)
- Check points listed alongside
Machine does not stop
and/or compressor
does not stop
Air
- Air hose defective
(hose cut? Air leaks from couplings?
- Compressor air supply low
- Jet air valve faulty (blocked in open position)
- Check the air hose and couplings in particular
and replace if necessary
- Check air lter (see para. 12)
- Check compressor relief valve
Machine stops after
starting up
Water
- Intake lter clogged
- Pressure reducer lter clogged
- Water hose too long and/or too narrow
- Water supply insufcient
- Check points listed alongside: clean lters,
check for adequate ow rate from the water hose
(at least 10-12 l/min if working with lime-cement
based plaster, at least 15-20 l/min with gypsum
based plasters) and replace hose if necessary or
collect water from an auxiliary tank