PREFACE Page P-7
P
LS300 User’s Guide
Petroleum absorbent and absorbent rags, and approved waste containers
Gasoline/oil resistant, non-hardening, UL Classified, Pipe Dope / Thread
Sealant (Gasoila) to seal threads of the LSU300 transducer & Needle Valve Kit
Single scale, general purpose, Pressure Gauge (1/4 inch NPT, 0 to 60 psi in 1 psi
increments) for temporary installation during site assessment and during the
LS300 Auto-Learn calibration step
Approved Gasoline/fuel oil container test tank (minimum 5-gallon capacity) to
collect product from the leak generator calibration kit during Auto-Learn calibration
Level, measuring tape, scribes/punch, and fasteners for wall mounting of console
Threaded 3/4 inch NPT (DN20NPT) rigid metal conduit, conduit bender, conduit
cutter, couplings, fittings, plus Epoxy Y Seal fittings (EYS), quick set epoxy, and
Conduit Clamps/Hangers
Explosion / Weather Proof J-Boxes
LSU300 Transducer Cable: Belden* shielded cable #9363-22AWG,
#9364-20AWG, or #9365-18AWG or equivalent (#9365-18AWG is preferred)
RS-485 Cable – for ATG and Pump Controllers – use the Transducer Cable above
#9365-18AWG preferred. Shield wire is connected to RS-485 “Ground” terminal on
the TPI board (The other end of the sheild is not connected).
Wire for LS300 Auto-Learn LLD console: Power Input and Hook Inputs — per code
Electricians tools (Safety Lockouts &Tags, assorted wire strippers, cutters, various
size – flathead and phillips-head screwdrivers, multimeter with leads & clips, strain-
relief fittings, spanner wrenches, slip-joint pliers [Non-sparking] conductor markers,
and indelible fine point marking pens)
* Belden is a trademark of Belden Technologies, Inc.