ELECTRONIC CONTROL
Compressor station
Functions and features.
This is an electronic device which has the function of piloting the motor of the compressor and
carrying out all the controls and electrical protection of the system.
Its main features are as follows:
a) Protection of the battery through automatic turning off of the compressor when the feeding
voltage reaches the minimum threshold.
The compressor will start up again automatically when the voltage goes back to normal values.
Note: these values have been measured at control unit input and/or on the DC socket.
BATTERY
PROTECTION
CUTOUT
12V
CUTIN
12V
CUTOUT
24V
CUTIN
24V
LOW
11.1 12.4 24.3 25.7
MED
10.4 11.7 22.8 24.2
HIGH
9.6 10.9 21.3 22.7
Setting up the battery protection
With the device switched off, press and hold the ON/OFF
and MAX/ECO buttons for
3 seconds to enter the battery protection selection menu. You can select the battery protection
level with the and buttons.