What to do if the test button is pressed on my Ingersoll-Rand ENL 5 Vario, but no condensate is discharged?
- JJason JohnsonAug 5, 2025
If you press the test button on your Ingersoll-Rand Heat Pump and no condensate discharges, possible causes include: * A blocked feed and/or discharge pipe: Check these pipes for obstructions. * Wear and tear: Check whether the valve opens audibly by pressing the test button several times for more than 2 seconds. * A defective circuit board: Check the circuit board for damage. * Operating pressure issues: Verify that the operating pressure is neither too low nor too high.