EasyManua.ls Logo

Interklima PCE 03 - Page 10

Interklima PCE 03
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interklima Terminal Units
PCE -VS ñ Hydronic cassette
10
Qw 1/h
232
270
312
409
475
549
591
686
790
768
895
1028
Pf kW
3.29
3.82
4.39
5.60
6.52
7.53
7.95
9.20
10.62
10.30
11.95
13.79
Tad
32.7
32.0
31.3
43.0
41.9
40.8
53.4
51.8
50.1
63.9
61.9
59.7
Pf kW
2.98
3.46
4.00
5.25
6.10
7.05
7.59
8.80
10.14
9.85
11.48
13.20
Tad
33.3
32.7
32.1
43.5
42.4
41.3
53.9
52.3
50.6
64.0
62.0
59.9
Pf kW
2.69
3.11
3.57
4.92
5.71
6.59
7.21
8.35
9.59
9.51
11.03
12.73
Tad
34.0
33.4
32.8
44.0
43.0
41.9
54.2
52.7
51.0
64.5
62.5
60.5
Pf kW
2.39
2.77
3.17
4.57
5.30
6.12
6.82
7.92
9.12
9.10
10.57
12.20
Tad
34.7
34.2
33.6
44.4
43.5
42.5
54.5
53.1
51.5
64.7
62.8
60.9
DpwkPa
0.914
1.200
1.550
2.530
3.320
4.310
4.920
6.420
8.300
7.870
10.400
13.300
Qa[m3/h]
692
842
1022
690
841
1023
692
842
1024
692
845
1022
PCE-09
Twi
40
50
60
70
TAI 18 TAI 20 TAI 22 TAI 24
PCE-09
Qw 1/h
256
298
343
452
526
608
650
757
875
848
988
1142
Pf kW
3.62
4.21
4.84
6.19
7.21
8.32
8.75
10.21
11.78
11.32
13.18
15.26
Tad
32.3
31.5
30.78
42.4
41.2
39.9
52.6
50.8
49.1
62.7
60.4
58.2
Pf kW
3.29
3.83
44.00
5.80
6.75
7.80
8.34
9.72
11.23
10.98
12.68
14.66
Tad
33.0
32.3
31.6
42.9
41.7
40.6
53.0
51.2
49.6
63.0
60.8
58.7
Pf kW
2.96
3.45
3.97
5.41
6.31
7.28
7.92
9.23
10.67
10.44
12.18
14.07
Tad
33.7
33.1
32.5
43.4
42.3
41.2
53.3
51.7
50.1
63.3
61.2
59.1
Pf kW
2.63
3.06
3.53
5.03
5.87
6.76
7.50
8.74
10.10
10.00
11.67
13.47
Tad
34.4
33.8
33.3
43.9
42.7
41.8
53.7
52.1
50.6
63.6
61.5
59.6
DpwkPa
1.09
1.44
1.84
3.03
3.98
5.17
5.83
7.68
9.96
9.41
12.30
16.10
Qa[m3/h]
782
962
1172
783
962
1170
781
963
1172
782
960
1171
PCE-10
Twi
40
50
60
70
TAI 18 TAI 20 TAI 22 TAI 24
PCE-10
NOTES
TAI: Air in temperature Qw: Fluid flow rate in heat exchanger Qa: Air flow Pf: Total cooling capacity
TWI: Fluid in temperature Dpw: Pressure drop standard coil tad: Discharge air dry bulb temperature
Design and specification are subject to change without prior notice for product improvement