RBU100H operation manual 6 Function parameters
-19-
Code
Name
Detailed instruction
Default
Modify
P0.13
Corresponding output
of lower limit of AO
0.00V10.00V
0.00V
P0.14
Upper limit of AO
output
0.0%100.0%
100.0%
P0.15
Corresponding output
of upper limit of AO
0.00V10.00V
10.00V
P0.16
Running mode of the
cooling fan
01
0:Operate after starting
1:Start when the temperature of the
heat sink exceeds 45°C
1
P0.17
Y switch output
selection
015
0:No output
1:Operation command valid
2:Regenarative output
3: Reserved
4:Fault output
515: Reserved
0
P0.18
RO selection
4 (fault
output)
P0.19
UV protection
300.01500.0V
380V voltage degree
660V voltage degree
380.0V
470.0V
P0.20
Fault reset times
03
0
P0.21
Fault reset time
0.110.0s
3.0s
P0.22
Reserved
P0.23
Regenerative current
limit
100500
330
P0.24
Operation time
0XXXXXH
P0.25
Function parameters
reset/fault history
clear
02
0: No change
1: Reset
2: Fault history clear
0
P0.26
Software version