RBU100H operation manual 6 Function parameters
-18-
6 Function parameters
6.1 Function code
Code
Name
Detailed instruction
Default
Modify
P0.00
Control mode
01
0: Keypad
1: Terminal
S1 valid: automatic operation
S2 valid: manual operation
1
P0.01
Keypad control
01
0: Automatic operation
1: Manual operation
0
P0.02
Filter time
110
1
P0.03
DC bus voltage
establishment time
010000ms
10000ms
P0.04
Regenerative voltage
difference during
starting
0.0240.0V
380V voltage degree
660V voltage degree
40.0V
60.0V
P0.05
Regenerative voltage
difference during
stopping
0.0120.0V
380V voltage degree
660V voltage degree
10.0V
15.0V
P0.06
Regenerative stop
time
0.110.0s
1.0s
P0.07
Input frequency
0~1
0:50Hz
1:60Hz
0
P0.08
S3 function
115
3:Valid when connect S3 to COM
Other reserved
3 (external
fault)
P0.09
S4 function
115
2: Valid when connect S4 to COM
Other reserved
2 (fault
reset)
P0.10
Reserved
1
P0.11
AO output
08
0: DC
voltage(01000V/1500V/3000V)
1: Output current (0200.0%)
28: Reserved
1
P0.12
Lower limit of AO
output
0.0%100.0%
0.0%