Electrical Installation Requirements - Model IWF055 (M-speed)
Only trained personnel should perform this
procedure. Use caution while servicing
machines with covers removed and power
applied.
W700
WARNING
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm
2
kW Standard
Heating Elements
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm
2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 1.6 10 6 14/2.5
6x3 kW
29.8 40 32
12/4.0
P 380-415 50/60 3 3+N+PE 1.6 10 6 14/2.5 34.2 40 40
12/4.0
Q 200-240 50/60 3 3+PE 4.0 10 6 14/2.5 53.3 50 63
10/6.0
X 200-240 50/60 1/3 2/3+PE 4.0 10 6 14/2.5 N/A N/A N/A
N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW
+
3x2 kW
25.1 30 25
14/2.5
P 380-415 50/60 3 3+N+PE 28.8 40 32
12/2.5
Q 200-240 50/60 3 3+PE 45.0 40 50
12/4.0
X 200-240 50/60 1/3 2/3+PE
N/A
N/A N/A
N/A
N 440-480 50/60 3 3+PE
3x3 kW
+
3x4 kW
34.5 40 40
12/4.0
P 380-415 50/60 3 3+N+PE 39.7
50 40
12/4.0
Q 200-240 50/60 3 3+PE
N/A
N/A N/A
N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A
N/A
N 440-480 50/60 3 3+PE
6x2 kW
20.4 25 20
14/2.5
P 380-415 50/60 3 3+N+PE 23.4
30 25
14/2.5
Q 200-240 50/60 3 3+PE
36.8
40 40
12/4.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A
N/A
N 440-480 50/60 3 3+PE
6x4 kW
39.2 50 40
12/4.0
P 380-415 50/60 3 3+N+PE 47.5
60 50
10/6.0
Q 200-240 50/60 3 3+PE
N/A
N/A N/A
N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A
N/A
Table 15