21 of 30
4.6 Heating the needle probe
Pressing this area enables selection of a needle
probe, or probes, heating cycle.
This cycle can also be run automatically if the key is
pressed during conservation, following a blast chilling/defrosting
cycle.
The function can be activated by parameter and can only be used
if u1=2 or u3=1. If cabinet sterilisation has also been enabled, the
needle probe heating icon is shown if the temperature recorded by
the needle probe is above 0°C .
The needle probe heating output is activated at maximum for the
time set by parameter u8 or until the temperature indicated by the
needle probe has reached that set by parameter u7.
At the end of heating, the buzzer sounds.
Heating can be stopped by pressing the key.
4.7 Drying
Pressing this area enables selection of a drying
cycle.
This is a cycle of forced-air ventilation that can be activated with
the door closed and for a duration set by parameter u13. If the
door is opened during drying this does not affect the cycle.
The cycle stops when the prescribed time has elapsed or when the
key is pressed.