Series PS-851
for Hot Water Boilers
Probe Type Low Water Cut-Offs
Applications:
Residential and Commercial
PS-851 models can be used as secondary low water cut-offs
on steam boilers with pressures up to 15 psi
®
Before using this product read and understand instructions.
Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of plumbing, steam, and electrical equipment and/or systems
in accordance with all applicable codes and ordinances.
To prevent flooding, do not use manual reset models with electric automatic water feeders.
To prevent electrical shock, turn off the electrical power before making electrical connections.
This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low water
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.
When installing jumper wire make sure you are not introducing a second voltage source
into the burner circuit and thereby bypassing other safety, limit, and operating controls.
When using mixed voltages, remove the factory installed jumper wire between terminal (H)
and (C), or between (1) and (2) on old Model PS-801-120.
Failure to follow this warning could cause property damage, personal injury or death.
WARNING
CAUTION
!
WARNING
U.S. Pat. No. 6,571,625
McDonnell & Miller
Installation & Maintenance
Instructions
MM-202(N)
Question and Answer IconNeed help?

Do you have a question about the ITT Series PS-851 and is the answer not in the manual?

ITT Series PS-851 Specifications

General IconGeneral
BrandITT
ModelSeries PS-851
CategoryBoiler
LanguageEnglish

Summary

Product Specifications

Operating Conditions and Model Features

Details temperature, humidity, and specific features for PS-801 and PS-851 models.

Electrical Ratings and Control Parameters

Outlines electrical ratings, control voltage, probe sensitivity, and power consumption.

Installation Guide

Tools and Probe Installation

Lists required tools and covers locating and installing the probe.

Control Box Mounting and Wiring

Details mounting the control box and connecting probe and control wiring.

Testing Procedures

Amber (Test) Light Model Testing

Tests models with low water and amber indicator lights, including burner circuit checks.

Green (Power) Light Model Testing

Covers start-up, manual testing, and test button usage for PS-801/851 green light models.

Troubleshooting and Maintenance

Diagnostic Checks and Cautions

Provides steps for diagnosing operational failures and important cautions.

Maintenance Schedule and Probe Cleaning

Outlines the recommended schedule for testing, inspection, and component replacement.