START UP OPERATIONS
The boiler first start up operation must be carried out by professionally
qualified personnel. Later, it will start automatically.
The user, for instance, may need to re-start the boiler personally after a long
period of inactivity.
Therefore, ensure:
- that the fuel and thermal plant water cocks are open;
- that the hydraulic system pressure when not working is over 1 bar and
lower than the boiler max allowed limit;
- that the boiler regulation thermostat is set between 60 and 90°C;
- that the environment thermostat is “ON” and set on 20°C;
- that the plant pumps are not blocked.
Turn on the main general switch and later the main switch from the control
panel.
The appliance will run an ignition cycle which will last until set temperatures
have been reached.
After this operation has been completed, the system will run automatically.
In case of ignition failures or malfunctioning, turn off the appliance and contact
professionally qualified personnel.
PRELIMINARY OPERATIONS PRIOR TO STARTING UP FOR THE
FIRST TIME
Before starting up:
- check that the gauges of setting and control instruments have been
correctly positioned in the bulbs;
- ensure that the turbolators do not protrude from the front of smoke
tubes;
- check that the plant has been filled with water, de-areated and that
pressure is over 1 bar and lower than the instrument max. allowed
pressure;
- check that all control and safety devices are working efficiently and
calibrated appropriately;
- check that the furnace is free from foreign matters;
- ensure that door refractory casing is not broken;
- check that the burner tube has been plugged correctly (see page 19);
- check that the door has been closed correctly (see page 26);
- check that the plant on-off valves are completely open and pumps turn
correctly;
- ensure that fuel is available and fuel cocks are open.