INSTALLATION
AND
OPERATION MANUAL
Z-600 Six Zone Comfort System™
READ THIS MANUAL THOROUGHLY BEFORE PROCEEDING WITH INSTALLATION
INTRODUCTION
The Z-600 Comfort System™ is a residential and light commercial forced air zone control system that allows a
single HVAC unit to have up to six separate zones. The system can be expanded to as many as 12 zones by
adding 3-zone expansion modules. Intuitive firmware allows the panel to be used with single stage, multi-stage,
heat pump and dual fuel equipment having up to 3 stages of heating and 2 stages of cooling. Standard heat / cool
or heat pump thermostats can be used with the Z-600, along with a choice of two or three-wire zone dampers.
Simple slide switch configuration allows for a wide range of system setup and control options best suited for each
zoning application. Additional features include, fuse protected inputs and outputs, easy-to-read and access wiring
terminals, LED
stat
us indication of all system functions, time delay override, adjustable on-board limits, balance
point controls, and selectable ventilation and purge modes. An adjustable upstage timer allows single stage
thermostats to be used with multi-stage equipment. Capacity Control can also stage equipment based on the
number of zones calling. The Z-600 comes in an attractive and rugged 2-piece anodized aluminum enclosure that
provides easy access for wiring, system setup and diagnostics.
WARNING
1. Turn power off to HVAC unit and control panel during installation to prevent serious injury from electrical shock
and/or damage to system.
2. Use extreme care when making duct openings and handling sheet metal to avoid injury.
3. The Z-600 and all components must be installed in a con
ditioned space
where the ambient temperature will not
exceed 150°F.
4. Install all components in a manner that prevents access by children.
CAUTION
1. Installation of this system must be in compliance with all applicable codes.
2. HVAC system must be properly sized and balanced to assure optimum system performance.
3. A bypass damper must be installed to maintain proper system airflow and static pressure.
4. All low voltage wire must be 18 gauge or heavier.
5. All wiring should be color coded and tagged for proper identification.
6. When landing wires to the control panel make sure wires are snug but do not over-tighten screw terminals.
CONTROL PANEL MOUNTING
Mount the zone control panel on a flat, moisture-free surface in a conditioned space that will facilitate easy access
for wiring and
system
setup.
CONTROL PANEL TRANSFORMER
1. Never use the 24 volt equipment transformer to power the control panel, regardless of it VA rating
.
2. Wire a separate 24 VAC transformer of the proper VA to the designated terminals on the zone control panel
marked 24 VAC.
ZONE CONTROL MADE SIMPLE™
SYSTEMS
Question and Answer IconNeed help?

Do you have a question about the Jackson Systems Z-600 and is the answer not in the manual?

Summary

Introduction

Installation Procedures

Zone Damper Wiring

Details wiring, types, and transformer VA for zone dampers.

Zone Thermostat Wiring

Specifies thermostat compatibility and wire gauge for zone thermostats.

Remote Sensor Connections

Covers mounting and wiring for Discharge Air and Outdoor sensors.

HVAC Unit Interface

Instructions for wiring the HVAC unit to the control panel.

System Status LED Functions

Sequence of Operation

Cooling Priority Mode

System prioritizes cooling calls over heating calls.

Majority Wins Mode

System mode determined by the majority of zone calls.

System Setup and Configuration

System Switch Settings

Explains the function of twelve slide switches for HVAC configuration.

Time Share Mode Operation

How Time Share mode operates with Majority Wins or Cooling Priority.

Fan Mode Control Options

Controls ventilation air flow based on thermostat fan settings.

Capacity Control Settings

How switches control second stage activation based on zone calls.

Stage Timer Functionality

Activates the Stage Timer for multi-stage equipment with single-stage thermostats.

Adjustable Temperature Limits

Describes High/Low limits for DAS and balance points for OTS sensors.

Thermostat Wiring Diagrams

Time Delay Parameters

Operational Limit Behavior

Heat Pump and Dual Fuel System Usage

Reversing Valve Configuration

Setting the reversing valve for heat pump operation.

Auxiliary Heat Wiring

Wiring auxiliary heat terminals for heat pumps.

Auxiliary Heat Control Logic

How auxiliary heat operates in different modes.

Balance Point Control Logic

Setting balance points for dual fuel and heat pump operation.

Emergency Heat Mode Operation

How to use and reset the emergency heat mode.

Panel Fuse Information

Information on 4 AMP and 2 AMP panel fuses.

Jackson Systems Z-600 Specifications

General IconGeneral
Product TypeZone Control Panel
Output Voltage24VAC
Transformer40VA
Thermostat Compatibility24V Thermostats
Input Voltage120VAC