Manual
EVO controller
25
www.jakkagroup.com
R/W
R/W
R/W
R/W
OFF(0) or 50-300 (0,1 °C)
TEMPERATURE SET POINT (IF AIR POST-TREATMENT IS PRESENT
ONLY)
B00-06: REMOTE_SUPPLY_SPEED
0-100%
B07: SUPPLY_SPEED_REMOTE_CONTROL
0: OFF
1: ON
B14-08: REMOTE_ EXHAUST_SPEED
0-100%
B15: EXHAUST_SPEED_REMOTE_CONTROL
0: OFF
1: ON
0-100%
50-400 (0,1 °C)
RHUMIDITY_-
SET_POINT
TEMPERATU-
RE_FREE
SET_POINT**
PARAMETER
TO COMMAND INDEPENDENTLY FANS SPEED FROM THE
LOGIC CONTROL .
HUMIDITY SET-POINT (IF DEHUMIDIFY FUNCTION PRESENT ONLY)
SET TEMPERATURE AS 52, ARE CORRELATED. THE DIFFERENCE IS
THAT CAN NOT BE SET TO 0 BECAUSE REPRESENT ALSO FREE
COOL\HEAT SET.
52
53
0-14400 (sec.)
R/W
MAXIMUM FAN SPEED
54
55
56
UNIT_1_DATA
81
TEMP_E (0,1 °C)
R
82 TEMP_R (0,1 °C)
R
83
TEMP_X (0,1 °C)
R
84
TEMP_I (0,1 °C)
R
85
TEMP_W (0,1 °C)
R
BYPASS STATUS.
86 STATUS_
FLAGS
R
87
R
88
R
89 (%)
R
R
90 B00: COMM_X540_FAIL
B01: TE_FAIL
B02: TR_FAIL
B03: TX_FAIL
B04: FILTERS_FAIL
B05: FANS_FAIL
B06: AUTO_FAIL
B07: TI_FAIL
COMMUNICATION ERROR IN X540 BOARD.
EXTERNAL AIR PROBE LINE FAILURE.
RETURN AIR PROBE LINE FAILURE.
EXPELLED AIR PROBE LINE FAILURE.
CLOGGED FILTERS ALARM.
FAN FAILURE .
AIR/HUMIDITY QUALITY SENSOR FAILURE.
INPUT PROBE LINE FAILURE.
TEMPERATURE
SET_POINT**
TIMER
SPEEDS
REMOTE
CONTROL
INPUT AIR TEMPERATURE
WATER TEMPERATURE
SUPPLY FAN INDIPENTENTLY CONTROL ENABLE
B00: BY-PASS
B01: SUPPLY_SPEED_REM_CONT_ACTIVE
B02: EXHAUST_SPEED_REM_CONT_ACTIVE
B03: DEHUM_OM
B04: NOFROST_ACTIVE
B05: EXT_DI_HUMIDITY
B06: EXT_DI_PIR_MIN
B07: EXT_DI_REMOTE_OFF
B08: HEAT_1
B09: HEAT_2
B10: TEMP_WATER_LOW
B11: EXT_DI_SUMMER
B12: EXT_DI_FIRE
B13: EXT_DI_WATER_NOFROST
B14: EXT_DO_AUTO_COMPARE
RECOVERY FAN INDIPENTENTLY CONTROL ENABLE
DEHUMIDIFY FUNCTION ENABLE
ANTIFROST HEAT EXCHANGER STATUS
DIGITAL INPUT STATUS: HUMIDITY
DIGITAL INPUT STATUS: PIR
DIGITAL INPUT STATUS: REMOTE
DIGITAL INPUT STATUS: HEATING/COOLING
STAGE 2 STATUS POST-HEATING
WATER COIL POWERED ANTIFROST STATUS
DIGITAL INPUT STATUS: SEASON
DIGITAL INPUT STATUS: FIRE
DIGITAL INPUT STATUS: WATER COIL POWERED ANTIFROST
STATUS
DIGITAL OUTPUT STATUS: AUTO CMP
EXPELLED AIR TEMPERATURE
EXHAUST AIR TEMPERATURE
EXTERNAL AIR TEMPERATURE
SPEED_C_
VALUE
IF FANS_FAIL_TACH (REG 7-B08) IS
SET TO 1 RPM, OTHERWISE %
DELIVERY FAN SPEED IN REVOLUTIONS OR
PERCENTAGE - SEE REG. 7-B08
EXHAUST FAN SPEED IN REVOLUTIONS OR
PERCENTAGE SEE REGISTER 7-B08
PERCENTAGE OF INPUT VALUE FOR:
QUALITY SENSOR
HUMIDITY SENSOR
EXT SIGNAL
IF FANS_FAIL_TACH (REG 7-B08) IS
SET TO 1 RPM, OTHERWISE %
SPEED_D_
VALUE
AUTO_INP
UT_VALUE
ALARMS 1