PROWLER SPECIFICATIONS
Model #: LD 5000
Name: PROWLER Leak Detector, Refrigerant Gas
Sensitivity: 0.025 oz/yr R-22, 0.05 oz/yr R-134a,
0.0125 oz/yr R-1234yf, 0.05 oz/yr R-410A,
0.05 oz/yr R-404A, 0.05 oz/yr R-407A,
0.05 oz/yr R-427A
Sensor Life: > 10 years (normal use)
Response Time: Instantaneous
Power Supply: 4 AA Alkaline batteries
Battery Life: 4.5 hours continuous
Warm Up Time: < 20 seconds
Probe Length: 17”
LCD Display: Sensitivity, Battery Light, Leak Level Indication
Weight, lbs.: 1lb. 3.4 oz.
Warranty: 2 years includes sensor
EN 14624 TEST SPECIFICATIONS
Min/Max Sensitivity 1 gm/yr minimum, > 50 gr/yr maximum
Threshold (fi xed):
Min/Max Sensitivity 3 gm/yr minimum, > 50 gm/yr maximum
Threshold (moving):
Min Detection Time: Approximately 1 second
Clearing Time: Approx. 9 seconds after exposure to > 50 gm/yr
Min. Threshold after
Maximum Exposure: 1 gr/yr
Sensitivity Threshold in
Polluted Atmosphere: 1 gm/yr
Calibration Frequency: 1/yr check with calibrated leak Standard