RS T4F Diesel Generator
|
G220RS 15
Stand Alone Manual Mode Operation
Before Stopping
1. Check with other personnel on the job site
and let them know that power is being
turned off.
2. Make sure that the power shutdown will not
create any hazards by turning off devices such
as pumps, heaters, or lights that may need to
be kept on.
Stopping Procedure
Perform the procedure below to stop the
generator:
1. Turn off all loads to the generator.
2. Open the main circuit breaker. The power
available lamp will go off.
3 Press the ‘stop/reset’ button once. The
generator will stop after the specified cooling
time. Duration: 5min.
4. If ‘stop/reset’ button is pressed again then
generator will stop immediately.
5. Ready to load and generator available LED
indicators will go off.
6. Turn the battery isolator to ‘off’ position after
the engine has stopped.