Installation Instructions
LC-224
2
ISTISJCELC224 0.0
Technical Features
RANGE 15 m
HORIZONTAL COVERAGE 100°
LENSES
LODIFF
®
Fresnel Lens
POLY IR
®
4 material
LED green, yellow, red
ALARM DURATION 2 s
SELF-DIAGNOSTIC -
WALK TEST LED YES
MICROWAVE FREQUENCY 10.525 Ghz
MAXIMUM RADIO-
FREQUENCY POWER
+14 dBm
SOLID STATE RELAY YES
INTERNAL EOL RESISTORS -
CREEP ZONE DEVICE YES
CASE TAMPER YES
BACK TAMPER YES
ANTI-MASKING -
PULSE COUNTER YES
RFI PROTECTION 30 V/m
HEAT COMPENSATION YES
FULLY DIGITAL YES
SWIVEL YES
POWER SUPPLY
9-15 VDC / 56 mA
UL/ULC tested: 10.6-13 VDC / 56 mA
COVER MATERIAL ABS
PET IMMUNITY YES
OPERATING TEMPERATURE
0°C to 49°C
HUMIDITY 93% RH
DIMENSIONS 114 x 63 x 40 mm
101W. MORNINGSIDE DR. FORT WORTH, TX 76110, U. S. A. (817) 926-7474, FAX:(817)926-7146
fresnel technologies inc.
2003
SIDE VIEW:
2.1m
(6.8ft)
TOP VIEW:
10m
(33ft)
(50ft)
15m
FRONT VIEW:
(50ft)
15m
5m
(16ft)
jay
WP 0.9 GI 6 T1
PET IMMUNE ARRAY
(28.2ft)
8.6m
(15.7ft)
4.8m
(6.8ft)
2.1m
35.6mm
(1.4 in)
49.8 mm
(1.96 in)
12.5 mm
(0.49 in)
95°
5m
(16ft)
10m
(33ft)
(50ft)
15m
0
101W. MORNINGSIDE DR. FORT WORTH, TX 76110, U. S. A. (817) 926-7474, FAX:(817)926-7146
fresnel technologies inc.
2003
SIDE VIEW:
2.1m
(6.8ft)
TOP VIEW:
10m
(33ft)
(50ft)
15m
FRONT VIEW:
(50ft)
15m
5m
(16ft)
jay
WP 0.9 GI 6 T1
PET IMMUNE ARRAY
(28.2ft)
8.6m
(15.7ft)
4.8m
(6.8ft)
2.1m
35.6mm
(1.4 in)
49.8 mm
(1.96 in)
12.5 mm
(0.49 in)
95°
5m
(16ft)
10m
(33ft)
(50ft)
15m
0
4. CONNECTION AND SETUP
Dip LED --> off = LED off - on = LED on
Dip RANGE --> off = 15 m - on =7 m range
Dip PULSE --> off = 1 pulse - on = 2 pulses
Dip OR-AUTO* --> off-off = AND; on-off = OR; on-on = auto OR
Trimmer RANGE = used only for microwave. NOTE: The RANGE trimmer
may need to be adjusted to the maximum position in order to achieve maxi-
mum area of coverage as indicated in Figure 3.
TAMPER terminals: Normally closed contact that opens when you open the
detector cover or remove the detector from the wall
NC terminals: Normally closed contact that opens when the detector goes
into alarm status
NO terminals: Normally open contact that closes when the detector goes
into alarm status
SUPPLY terminals: Power supply 9-15 VDC / 56 mA. UL/ULC tested: 10.6-13
VDC / 56 mA. NOTE: For UL/ULC installations the detector shall be provided
with minimum of 4 hours of standby power from either a listed compatible
control unit or power supply. Output contacts ratings: 28 VDC / 100 mA. Use
only resistive loads on the outputs.
Note: Incorrect connections may result in failure or improper operation. Inspect wiring and ensure connections are correct before turning on the power.
* For UL/ULC installations use the OFF-OFF configuration only.
DEOL supervision
with type C alarm contact
NO (no EOL supervision)
Not used on UL/ULC
listed installations
DEOL supervision
with type C alarm contact
and device tamper
- Fig 3 -
ZxCOM
–
+
TAMPER
NO NC
LC-224
SUPPLY
–
+
CTAMPER
5.6 kohm
5.6 kohm
Negative connected
Tamper
Panel
Internally
connected
ZxCOM
–
+
TAMPER
NO NC
LC-224
SUPPLY
–
+
CTAMPER
5.6 kohm
5.6 kohm
Negative connected
Tamper
Panel
Internally
connected
Zx COM
–
+
TAMPER
NO NC
LC-224
SUPPLY
–
+
CTAMPER
Negative connected
Tamper
Panel
Internally
connected