30 Johnson Controls Ducted Systems
-10
(10)
208 15.6 110 24 3.03 9.6 5.5 20
None - - - 60.8 66.3 70 80
E18 13.5 2 37.5 71.4 78.3 80 80
E24 18 2 50 87 93.9 90 100
E36 25.5 2 70.8 113 119.9 125 125
E54 40.6 2 112.7 165.4 172.3 175 175
230 15.6 110 24 3.03 9.6 5.5 20
None - - - 60.8 66.3 70 80
E18 18 2 43.3 78.6 85.5 80 90
E24 24 2 57.7 96.6 103.5 100 110
E36 34 2 81.8 126.8 133.6 150 150
E54 54 2 129.9 154.4 161.3 175 175
460 7.8 52 12 1.6 4.7 2.2 20
None - - - 30.5 32.7 35 40
E18 18 2 21.7 39.3 42 40 45
E24 24 2 28.9 48.3 51 50 60
E36 34 2 40.9 63.3 66 70 70
E54 54 2 65 77.1 79.9 90 90
575 5.8 38.9 9 1.35 3.6 1.8 20
None - - - 23.4 25.2 25 30
E18 18 2 17.3 31.1 33.4 35 35
E24 24 2 23.1 38.4 40.6 40 45
E36 34 2 32.7 50.4 52.6 60 60
E54 54 2 52 61.5 63.8 70 70
-12
(12.5)
208 23.1 160 36 3.03 14 5.5 20
None - - - 88.1 93.6 110 110
E18 13.5 2 37.5 88.1 93.6 110 110
E24 18 2 50 92.5 99.4 110 110
E36 25.5 2 70.8 118.5 125.4 125 150
E54 40.6 2 112.7 170.9 177.8 175 200
230 23.1 160 36 3.03 14 5.5 20
None - - - 88.1 93.6 110 110
E18 18 2 43.3 88.1 93.6 110 110
E24 24 2 57.7 102.1 109 110 110
E36 34 2 81.8 132.3 139.1 150 150
E54 54 2 129.9 159.9 166.8 175 175
460 12.2 87 19 1.6 6.6 2.2 20
None - - - 45.5 47.7 50 50
E18 18 2 21.7 45.5 47.7 50 50
E24 24 2 28.9 50.6 53.4 60 60
E36 34 2 40.9 65.6 68.4 70 70
E54 54 2 65 79.5 82.3 90 90
575 8.7 62 14 1.35 5.2 1.8 20
None - - - 34.2 36 40 40
E18 18 2 17.3 34.2 36 40 40
E24 24 2 23.1 40.4 42.6 45 45
E36 34 2 32.7 52.4 54.6 60 60
E54 54 2 52 63.5 65.8 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZS-06 through -12 high static motor - with powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size (amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps