Do you have a question about the jokab safety Vital 1 and is the answer not in the manual?
Explains how to identify a Vital 1 safety module by checking its front panel and label.
Describes checking Vital 1 safety functions using connected devices and front panel LEDs.
Verify all five LEDs are ON when safety circuit is closed and devices are un-interrupted.
Check LEDs #2 and #4 turn OFF when safety devices are interrupted.
If LEDs #2 or #4 stay ON during interruption, the unit may be faulty.
Provides instructions for replacing a Vital 1 safety module.
Highlights detachable connection blocks for easy and safe replacement.
Ensure power supply to Vital 1 is disconnected before replacement.
Tighten screws and detach connection blocks using a screwdriver.
Release the unit from the DIN rail by manipulating the bottom latch.
Attach the new Vital 1 unit to the 35 mm DIN rail, ensuring the latch engages.
Slide connection blocks into the correct slots, ensuring cables are in place.
Reconnect power and verify operation by checking LEDs and safety outputs.
Confirm all safety devices work correctly and the replacement is finished.
| Supply Voltage | 24 V DC |
|---|---|
| Inputs | 2 safety inputs |
| Outputs | 2 safety outputs |
| Response Time | ≤ 20 ms |
| Reset | Manual or automatic |
| Width | 22.5 mm |
| Number of safety inputs | 2 |
| Number of safety outputs | 2 |
| Protection Class | IP20 |
| Safety Category | Cat. 4 |