4 Commissioning the instrument
11
Controller
Parameter Meaning
Value range
from...factory-set...to
Setpoint
target value of control action (temperature value, current or voltage)
... 0.0 ...
Hysteresis 0.2 ... 1.0 ... 99.9
Low setpoint limit
SP can be set down to this low limit.
-999 ... -50 ... +999
High setpoint limit
SP can be set up to this high limit.
-999 ... 500 ... +999
Controller type
: cooling controller
: heating controller
Switch-on delay after power-on
for staggered switch-on of several equipment units in a plant.
0 ... 60min