LB management
Display standard for room temperature control
Mo - Fr Sa - Su
ƙ 06:00 08:30 07:00 22:00
Ʀ 12:00 14:00 --:-- --:--
Ʊ 17:00 22:00 --:-- --:--
– Automatic mode is active
– Controller output depending on insert: room temperature controller insert = pulse width
modulation, switch insert = two-point control
– Internal temperature sensor for room temperature measurement is active
– Display switch-off after 2 minutes of inactivity (no button actuation) is active
6 Commissioning
Setting date, time and other parameters
When the year is flashing on the display, you must set or confirm the data listed in the table.
– Briefly press the
–
or
+
button to change values or toggle between
YES / No
.
– A long press of the
–
or
+
button accelerates value changes.
– Press the Ƨ button to go back in the menu.
– Press the ƨ button to apply the setting and call the next value. After editing the last para-
meter, all values will be saved and automatic mode will be invoked.
Parameters
Display icon Setting option/
Default setting
Year
ƛƜ 2019 or later
Month
ƛƜ 01 ... 12
Day
ƛƜ 01 ... 31
Hour
ƛƜ 00 ... 12 ... 23
Minute
ƛƜ 00 ... 59
Automatic summer time changeover
ƛƜ Ơ YES / No
Controller output
1)
ƛƜ Ƽ YES / No
Valve adaptation
2)
ƛƜ Ƹ NO / NC
Optimised heating up
Ʋ ƹ YES / No
Temperature drop detection
Ʋ Ʒ YES / No
Temp. unit
Ʋ °C / °F
Comfort temp.
Ʋ Ƶ 5 ... 21.0 ... 30 °C
ECO temp.
Ʋ ƶ 5 ... 18.0 ... 30 °C
Frost protection
Ʋ ƽ 5 ... 7.0 ... 30 °C
4 / 10