At the time of the burnout of the external sensor
Hot-air generator is stopped when the external sensor became the burnout of snapping of a wire etc. in the
case that the temp. of the place that parted is controlled by using the external sensor of the option.
"---" is flickered to HOT-AIR TEMP., "TC0" to
SETTING TEMP. (EXT. SENSOR lamp is being
lighted.)
Main cause
Snapping of a wire of the external sensor
Snapping of a wire of the external sensor
compensating wire
Miss of the inlet sensor wiring terminal
Return method
Please disarm by pushing STOP switch after the
confirmation of the external sensor.
Reverse connection by each sensor or detection of minus temp.
Hot-air generator is stopped at the time of the reverse connection of each temp. sensor (External sensor is
included) or perception of -15
C. (Only inside temp. sensor is -10
C.)
"---" is flickered to HOT-AIR TEMP, display of each
sensor to SETTING TEMP
External sensor
: Tc0 Outlet sensor : TcA
Overheat sensor
: TcM Inlet sensor : Tcc
Inside temp. sensor
: Tcb
Main cause
Reverse connection of the external sensor
Reverse connection by the wiring readjustment of
each sensor
Atmosphere temp. or suction temp. of minus
Return method
P
lease disarm by pushing STOP switch after the
confirmation of the external sensor or the
improvement of the minus condition. Please
order the repair about except for reverse
connection o
f
the external sensor.
Attention : Please block the source power supply (factory power supply) without fail when the
wiring is confirmed and readjusted at the time of abnormal.
-14-