DE Einbau- und Bedienungsanleitung 2
KHS Hygienespülung PRO
KHS Hygienespülung PURE
KHS Hygienespülung LITE
Fig. 689
EN Installation and operating instructions 14
KHS Hygiene Flush Box PRO
KHS Hygiene Flush Box PURE
KHS Hygiene Flush Box LITE
Fig. 689
FR Instructions d’installation et d’utilisation 26
KHS Hygiene Flush Box PRO
KHS Hygiene Flush Box PURE
KHS Hygiene Flush Box LITE
Fig. 689
IT Istruzioni di montaggio e d‘uso 38
KHS Hygiene Flush Box PRO
KHS Hygiene Flush Box PURE
KHS Hygiene Flush Box LITE
Fig. 689
NL Inbouw- en bedieningshandleiding 50
KHS Hygiene Flush Box PRO
KHS Hygiene Flush Box PURE
KHS Hygiene Flush Box LITE
Fig. 689

Table of Contents

Other manuals for Kemper KHS Hygiene Flush Box PRO

Questions and Answers

  • J
    Jacob HillAug 9, 2025
    Why is my Kemper Construction Equipment aerator dripping?
    • J
      Jessica HodgesAug 9, 2025
      The aerator might be dripping because the solenoid valve isn’t closing properly. Try removing the solenoid valve and cleaning it, replacing it if necessary.
  • V
    Victor HillAug 14, 2025
    What to do if there is an odour from my Kemper Construction Equipment?
    • C
      charlesbellSep 12, 2025
      If you notice an odour, it could be due to a lack of water in the trap. Perform a manual flushing. Alternatively, the anti-siphon trap might not be fitted correctly; ensure it is properly installed.
  • A
    Andrew WalkerAug 19, 2025
    How to fix a Kemper Construction Equipment reversible cover that doesn’t close flush with the wall?
    • A
      Aaron MontesAug 19, 2025
      If the reversible cover doesn’t close flush with the wall, it could be due to several reasons: * The magnetic safety catch might not be installed correctly, or only one of the catches moved. Install the magnetic safety catch correctly and ensure both catches are in the same position. * There might be plaster residue in the frame. Remove any plaster residue from the frame. * The guide bolts under the reversible cover might not be inserted in the holes provided in the FM frame. Insert the guide bolts into the appropriate holes.
  • L
    lawrenceadamAug 25, 2025
    What to do if the float switch triggers a fault signal in my Kemper Construction Equipment?
    • B
      Brenda MillerAug 25, 2025
      A fault signal from the float switch could indicate backflow in the connected drainpipe or trap due to clogging. Check whether the drainpipe was designed according to DIN 1986-100 in conjunction with EN 752 and EN 12056. Manually check the float switch and also check the cable connection from the float switch to the controller.
  • P
    Patrick MurrayAug 29, 2025
    How to fix no water from Kemper Construction Equipment aerator?
    • T
      Terri CordovaAug 29, 2025
      If there's no water coming from the aerator, it might be because the FL is installed the wrong way round. Ensure you install the FL correctly, with the aerator’s outer gasket pointing in the direction of flow (upwards).
  • E
    Erica MorrisSep 3, 2025
    How to fix no clean spray cone from Kemper Construction Equipment aerator set?
    • J
      Jeffrey DavisSep 3, 2025
      If you're not getting a clean spray cone from the aerator set, it could be due to calcification of the FL or aerator. Try cleaning the FL/aerator, and replace it if necessary. It also may be caused by non-compliance with the recommended replacement interval or clogging.

Kemper KHS Hygiene Flush Box PRO Specifications

General IconGeneral
Power Supply24V DC
Operating Temperature5 - 40 °C
Flush TimeAdjustable
Flush IntervalAdjustable
Connection1/2" BSP
Flush VolumeAdjustable
Water ConnectionG 1/2"