industry controller KFM 92 / KFM 93 B 9200 E
operating instructions - page 1 -
_______________________________________________________________________
data subjects to alteration 9200E1.DOC / 2010103
1 Digital display actual value
2 2nd digital display (if active)
3 LED-display relay function
4 Key for setpoint and parameter mode
5 Setpoint adjustment
6 Parameter mode lock switch (back face)
Certifications: DIN, BV, DNV, GL
3
1
2
4 5
6
Brief description:
KFM 92 is a microprocessor based industry controller series in panel mounting- format 96 x 96 mm.
Design and operating elements are especially devised for easy and convenient handling and operation.
An assembly system renders possible the simple basic version as well as a plurality of variants with
up to 8 relays, several digital and analog out- and inputs and other additional devices. All relay contacts are
implemented as potential-free changeover contacts. Depending on the version, external RC combinations are
included, internal RC combinations for optional connection to terminals (N.O. contact factory- connected) or the
N.O. contacts of all relays are permanently wired internally with RC combinations.The scope of delivery includes
plugable terminal blocks.
Types:
(depending on configuration*): type:
indicator 9201.
one stage controller 9210.
two stage controller 9220.
heating / cooling controller 9230.
positioner / follow-up controller 9240.
two- point- PID controller 9250.
three- point- PID controller 9260.
three- point- step controller 9270.
continuous controller 9280.
continuous controller, 2 outputs 9281.
Sub-types: suffix (*)
basic function .0
basic function + 1 additional contact .1
basic function + 2 additional contacts .2
2 x basic function .3
extension: logic output ..L
function extensions suffix (*)
cascade controller 991k
program controller 991p
ramp set point value 991r
step controller 991t
Additional devices: (*)
additional analog inputs (99) a
external set value incl. switch-over (99) bwa
second set value incl. switch-over (99) bwz
binary input to switch special functions (99) b..
additional switching contacts (99) f..
analog signal outputs (99) o.
serial interface RS 232/485 (99) s.
interface Profibus, Interbus S, other (99) sp/si.
* In case of more than 1 extension there is at the
data plate only once '99' , f.e. 92700-99aw-ogx-rü.
For more information see corresponding data sheets.
Inputs:
max. 4 measuring inputs, type suffix
acc. to sub-type:
Pt100 DIN, 0...400°C none (or 0)
Pt100 DIN, 0...100°C 1.
thermo couple Ni Cr NI (type K)0...1200°C n.
thermo couple Fe Cu NI (type J)0... 900°C f.
thermo couple Pt Rh Pt (type S)0...1700°C p.
feedback device 0...100 up to 1000 W w.
standard signal 0(4)...20mA, 0(2)...10V e.
combined input Pt100 / standard signal q.
Ranges:
Pt 100: 0...400°C, switchable to °F, optional: other
ranges; for standard signal range adjustable -999 to
4000. Setpoint ranges can be limited by menu
Displays:
2 four- figured digital displays, decimal point
adjustable, upper display: actual value, lower
display: other selectable data,
up to 8 LEDs for relays function display.
Display of function:
Hold down the P-key for more than 5 sec
to get a short-cut message of the configured function on
the display (=position 3-5 of list number)
(in case of locked parameter mode only ).
Measuring line monitoring:
Display "Err 1...4" in case of measuring line fault
and adjustable safety shut down of all outputs
Outputs:
up to 8 relays with potential free change over switch,
as control outputs or as additional contacts,
capacity: 250V 2A,
incl. spark extinction (for normally open contacts)
1-2 continuous outputs 0/4...20mA, 0/2...10V as
control or signal outputs(apparent ohmic load 500 W)
Question and Answer IconNeed help?

Do you have a question about the KFM 92 Series and is the answer not in the manual?

Summary

Installation and Operation

Installation and Wiring

Covers physical installation into panels and essential electrical wiring practices.

Troubleshooting Common Error Messages

Lists and explains error codes (Err 1-206) for diagnosing issues.

Parameter Configuration

Accessing Parameter Levels

Explains how to unlock and access parameter settings via a rear panel switch.

Optimization Procedures

Manual Optimization of Control Parameters

Guides on manually adjusting P, I, D parameters for optimal control performance.

Automatic Self-Adaptation Function

Explains the self-adaptation process for automatic determination of control parameters.